Powered by GoogleTranslate

Inspection Detail

Inspection: 2956472 - New Mexico Pole Line

Inspection Information - Office: State Of New Mexico Environment Department Occupational Health & Safety Bureau

 

Inspection Nr: 2956472
Report ID: 0653510
Date Opened: 05/03/1985

Site Address:
New Mexico Pole Line
Kruse Ranch
Wagon Mound, NM 87752

Mailing Address:
Po Box 352, Peralta, NM 87042

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 05/03/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/19/1986


Related Activity
Type Activity Nr Safety Health
Accident 360765457
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $240 $0 $0 $0 $0 $240
Current Penalty $240 $0 $0 $0 $0 $240
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 B01 08/05/1985 08/12/1985 $120 $120 $0 08/26/1985 -  
2. 01002 Serious 19260950 C01 08/05/1985 08/12/1985 $120 $120 $0 08/26/1985 -  

Investigation Summary

Investigation Nr: 14557375
Event: 05/01/1985
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU GROUND WIRE

A LINE CREW WAS REMOVING HARDWARE FROM OLD WOODEN POLES WHICH HAD BEEN REPLACED WITH NEW ONES. ONE EMPLOYEE WAS WORKING ON A POLE THAT WAS LYING 64 INCHES TO THE SIDE OF A POWER LINE INSTALLED 28 FEET OVERHEAD. THE EMPLOYEE HAD WRAPPED PLIERS AROUND THE GROUND WIRE AND WAS PULLING IT IN ORDER TO REMOVE IT. THE WIRE BROKE 25 FEET FROM THE TOP OF THE OLD POLE AND FLEW DIRECTLY ABOVE THE EMPLOYEE'S HEAD, STRIKING THE 7200-VOLT-TO-GROUND POWER LINE. HE WAS NOT WEARING INSULATED GLOVES OR BOOTS. CARDIO-PULMONARY RESUSCITATION WAS ATTEMPTED WITHOUT SUCCESS, AND THE EMPLOYEE DIED OF ELECTROCUTION.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, CPR, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2956472 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.