Powered by GoogleTranslate

Inspection Detail

Inspection: 18812156 - Blumenthal-Kahn Electric Ltd. Partnership

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 18812156
Report ID: 0352420
Date Opened: 01/19/1987

Site Address:
Blumenthal-Kahn Electric Ltd. Partnership
3901 Glidden Road
Baltimore, MD 21226

Mailing Address:
10233 S. Dolfield Road, P. O. Box 369, Owings Mills, MD 21117

Union Status: Union

SIC:1793

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/26/1987

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/22/1987


Related Activity
Type Activity Nr Safety Health
Accident 360752539
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $650 $0 $0 $0 $0 $650
Current Penalty $650 $0 $0 $0 $0 $650
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260556 B 2 V 03/18/1987 03/21/1987 $310 $310 $0 -  
2. 02001 Serious 19260954 F 03/18/1987 03/21/1987 $340 $340 $0 -  

Investigation Summary

Investigation Nr: 707117
Event: 01/16/1987
BURNS AND FALL - DIRECT CONTACT WITH OVERHEAD LINE

A JOURNEYMAN LINEMAN WAS ASSIGNED TO REPAIR HOT SPOTS IN OVERHEAD POWER LINES. THE LINEMAN WAS ASSISTED BY A GROUNDMAN WHO HAD BEEN GOING UP IN AN AERIAL LIFT WITH HIM. FOR AN UNKNOWN REASON, THE LINEMAN WENT TO A SUBSTATION WHERE NO PROBLEM HAD BEEN INDICATED. HE CLIMBED OUT OF HIS SUSPENDED BUCKET ONTO THE TOP STEEL OF THE SUBSTATION AND PLACED HIMSELF CLOSE TO ENERGIZED 34.5-KILOVOLT LINES. HE THEN TRIED TO USE A WIRE BRUSH TO CLEAN A DEENERGIZED 34.5-KILOVOLT CONNECTION WHICH WAS NEAR AN ENERGIZED 34.5-KILOVOLT LINE. HE RECEIVED AN ELECTRIC SHOCK AND BURNS TO HIS FINGERS, WRISTS, ANKLES, AND FEET. HE THEN FELL 25-FEET TO THE GROUND, CAUSING FRACTURES AND INTERNAL INJURIES. HE DIED THE NEXT DAY AS A RESULT OF HIS INJURIES.

Keywords: BURN, CLOTHING, ELECTRICAL, POWER LINE WORKER, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK, FALL, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18812156 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.