Powered by GoogleTranslate

Inspection Detail

Inspection: 17739897 - H And H Testing

Inspection Information - Office: Baltimore Area Office

 

Inspection Nr: 17739897
Report ID: 0316100
Date Opened: 02/08/1989

Site Address:
H And H Testing
Howard University (C.B. Powell Bldg)
Washington, DC 20059

Mailing Address:
9502 Deereco Road, Timonium, MD 21093

Union Status: NonUnion

SIC:7389

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/16/1989

Emphasis:

Case Closed: 05/17/1989


Related Activity
Type Activity Nr Safety Health
Accident 360371397
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 1 2 3
Initial Penalty $0 $16,000 $0 $0 $0 $16,000
Current Penalty $0 $2,000 $0 $0 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Willful 19100303 B01 VII 03/06/1989 03/06/1989 $8,000 $8,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Willful 19100308 A02 III 03/06/1989 03/06/1989 $2,000 $8,000 $0 I - Informal Settlement  
3. 02001 Other 19040002 A 03/06/1989 03/16/1989 $0 $0 $0 -  
4. 02002 Other 19030002 A01 03/03/1989 03/06/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14327951
Event: 02/03/1989
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

An employee was drawing a fluid sample from a transformer. The employer relied on the university, which owned the transformer, to deenergize it. The transformer primary was apparently opened. However, the employee's supervisor had not followed standard industry practice and company procedures to isolate the transformer; and the transformer terminals remained energized by backfeed. The employee contacted live parts on the transformer and was electrocuted. The employer defended the supervisor's actions because of the limited time it normally takes to perform the contracted function.

Keywords: VOLTAGE BACKFEED, ELECTRICAL, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 17739897 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close