Powered by GoogleTranslate

Inspection Detail

Inspection: 17721374 - Consolidated Petroleum Terminal, Inc.

Inspection Information - Office: Long Island Area Office

 

Inspection Nr: 17721374
Report ID: 0214700
Date Opened: 09/24/1987

Site Address:
Consolidated Petroleum Terminal, Inc.
Terminal/Bellmeade Road
East Setauket, NY 11733

Mailing Address:
, , 00000

Union Status: Union

SIC:5171

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/22/1987

Emphasis:

Case Closed: 02/08/1988


Related Activity
Type Activity Nr Safety Health
Referral 900838012 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $2,000 $0 $0 $2,000
Current Penalty $0 $0 $2,000 $0 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Repeat 19100307 B 12/08/1987 12/14/1987 $2,000 $2,000 $0 -  

Investigation Summary

Investigation Nr: 14562425
Event: 09/22/1987
EXPLOSION - UNAPPROVED EQUIPMENT USED IN HAZARDOUS LOCATION

AN EMPLOYEE WAS FILLING THE REFRIGERANT SECTION OF A GASOLINE VAPOR CONDENSATION SYSTEM WITH METHYLENE CHLORIDE. HE WAS USING A DAYTON 0.33-HORSEPOWER NON-EXPLOSION-PROOF MOTOR/PUMP, ATTACHED TO ITS SOURCE OF SUPPLY THROUGH A NON-EXPLOSION-PROOF-TYPE EXTENSION CORD SET. THE CORD SET WAS PLUGGED INTO AN ADAPTER CORD SET THAT HAD AN EXPLOSION-PROOF ATTACHMENT PLUG ON ONE END AND A NON-EXPLOSION-PROOF CONNECTOR ON THE OTHER END. THE EMPLOYEE WAS PUMPING THE METHYLENE CHLORIDE FROM 55-GALLON DRUMS IN THE BUCKET OF A BACKHOE. THE EMPLOYEE PLUGGED THE ADAPTER CORD SET, WHICH WAS 3 FEET LONG, INTO AN EXPLOSION-PROOF RECEPTACLE OUTLET ABOUT 100 FEET FROM WHERE HE WAS WORKING. HE THEN RAN THE EXTENSION CORD SET TO THE VAPOR RECOVERY UNIT. HE WAS STARTING HIS SEVENTH DRUM; AND, WHEN HE PLUGGED THE MOTOR'S POWER CORD INTO THE CONNECTOR ON THE CORD SET IN THE GASOLINE-ENRICHED ATMOSPHERE, THERE WAS AN EXPLOSION. THE EMPLOYEE SUSTAINED THIRD DEGREE BURNS OVER 40 PERCENT OF HIS BODY.

Keywords: E GI V, ELECTRICAL, METHYLENE CHLORIDE, CORD SET, ATTACHMENT PLUG, ELECTRIC PUMP, EXPLOSION, CORD CONNECTOR, GASOLINE, EQUIPMENT APPROVAL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 17721374 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.