Inspection Detail
Inspection: 17714619 - Remcon Plastics, Inc.
Inspection Information - Office: Allentown Area Office
Site Address:
Remcon Plastics, Inc.
1100 E. Hector Street
Conshocken, PA 19428
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3089
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/13/1989
Emphasis:
Case Closed: 09/11/1989
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360729370 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 10 | 9 | 19 | |||
Current Violations | 10 | 9 | 19 | |||
Initial Penalty | $2,650 | $0 | $0 | $100 | $0 | $2,750 |
Current Penalty | $2,350 | $0 | $0 | $100 | $0 | $2,450 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19100036 B04 | 08/04/1989 | 09/04/1989 | $250 | $250 | $0 | - | ||
2. | 01001B | Serious | 19100037 K02 | 08/04/1989 | 08/07/1989 | $0 | $0 | $0 | - | ||
3. | 01001C | Serious | 19100037 Q01 | 08/04/1989 | 08/25/1989 | $0 | $0 | $0 | I - Informal Settlement | ||
4. | 01002 | Serious | 19100101 B | 08/04/1989 | 08/07/1989 | $100 | $200 | $0 | I - Informal Settlement | ||
5. | 01003 | Serious | 19100212 A01 | 08/04/1989 | 09/04/1989 | $250 | $250 | $0 | - | ||
6. | 01004 | Serious | 19100212 A05 | 08/04/1989 | 09/04/1989 | $200 | $300 | $0 | I - Informal Settlement | ||
7. | 01005A | Serious | 19100215 A04 | 08/04/1989 | 09/04/1989 | $200 | $200 | $0 | - | ||
8. | 01005B | Serious | 19100215 A04 | 08/04/1989 | 08/07/1989 | $0 | $0 | $0 | - | ||
9. | 01005C | Serious | 19100215 B07 | 08/04/1989 | 08/07/1989 | $0 | $0 | $0 | - | ||
10. | 01006 | Serious | 19100219 B01 | 08/04/1989 | 09/04/1989 | $100 | $200 | $0 | I - Informal Settlement | ||
11. | 01007 | Serious | 19100219 F03 | 08/04/1989 | 09/04/1989 | $300 | $300 | $0 | - | ||
12. | 01008 | Serious | 19100303 G02 I | 08/04/1989 | 08/11/1989 | $350 | $350 | $0 | - | ||
13. | 01009 | Serious | 19100304 F04 | 08/04/1989 | 08/07/1989 | $350 | $350 | $0 | - | ||
14. | 01010 | Serious | 19100305 B01 | 08/04/1989 | 08/11/1989 | $250 | $250 | $0 | - | ||
15. | 02001 | Other | 19030002 A01 | 08/04/1989 | 08/07/1989 | $50 | $50 | $0 | - | ||
16. | 02002 | Other | 19040002 A | 08/04/1989 | 08/07/1989 | $50 | $50 | $0 | - | ||
17. | 02003 | Other | 19100036 B08 | 08/04/1989 | 09/04/1989 | $0 | $0 | $0 | - | ||
18. | 02004 | Other | 19100037 Q02 | 08/04/1989 | 08/25/1989 | $0 | $0 | $0 | I - Informal Settlement | ||
19. | 02005 | Other | 19100151 C | 08/04/1989 | 09/04/1989 | $0 | $0 | $0 | - | ||
20. | 02006 | Other | 19100303 E | 08/04/1989 | 08/07/1989 | $0 | $0 | $0 | - | ||
21. | 02007 | Other | 19100303 G01 II | 08/04/1989 | 08/07/1989 | $0 | $0 | $0 | - | ||
22. | 02008 | Other | 19100305 B02 | 08/04/1989 | 08/11/1989 | $0 | $0 | $0 | - | ||
23. | 02009 | Other | 19101200 E01 | 08/04/1989 | 09/04/1989 | $0 | $0 | $0 | - |
Investigation Summary
A 240-VOLT TRANSFORMER WAS GROUNDED BY A CONDUIT CONTAINING THE FEEDER FROM A 480-VOLT ELECTRICAL SUPPLY CABINET. AN EMPLOYEE WAS LYING ON TOP OF THE TRANSFORMER ENCLOSURE TO REACH BETWEEN THE TRANSFORMER AND THE SUPPLY CABINET TO PICK UP A PIECE OF SCRAP PLASTIC CONDUIT. THE FEEDER CONDUIT PULLED FREE OF THE TRANSFORMER ENCLOSURE, DISCONNECTING THE EQUIPMENT GROUNDING CONDUCTOR. AN APPARENT GROUND FAULT IN THE TRANSFORMER CAUSED THE ELECTROCUTION OF THE EMPLOYEE.
Keywords: E GI III, ELECTRICAL, CONDUIT, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, TRANSFORMER
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 17714619 | Fatality | Electric Shock | Occupation not reported |