Powered by GoogleTranslate

Inspection Detail

Inspection: 17445750 - Dan Morgan Concrete, Incorporated

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 17445750
Report ID: 0420600
Date Opened: 03/19/1985

Site Address:
Dan Morgan Concrete, Incorporated
9565 South Orange Blossom Trail
Orlando, FL 32809

Mailing Address:
1416 Grand Street, Orlando, FL 32805

Union Status: NonUnion

SIC:1771

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/20/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/17/1986


Related Activity
Type Activity Nr Safety Health
Accident 360649891
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1
Initial Penalty $560 $0 $0 $0 $0 $560
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260400 H01 04/16/1985 04/16/1985 $0 $560 $0 06/05/1985 R - Review Commission  
2. 02001 Other 19260401 C 04/16/1985 04/16/1985 $0 $0 $0 06/05/1985 R - Review Commission Citation has been deleted.

Investigation Summary

Investigation Nr: 14346126
Event: 03/14/1985
Electric Shock - Ground Fault in Utilization Equipment

A water cooler with a ground fault had been installed in the office trailer of a construction site. Connecting the cooler to a receptacle in the trailer energized the equipment grounding conductor run throughout the trailer. The next day, an employee used a rebar cutter supplied by an extension cord set that was plugged into another receptacle in the trailer. The trailer circuit was not protected by a ground-fault circuit interrupter. The case of the cutter became energized through the equipment grounding conductor in the cord set, and the employee was electrocuted.

Keywords: ELECTRICAL, ELECTROCUTED, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 17445750 Fatality Electric Shock Construction trades, n.e.c.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.