Inspection: 17429291 - Montenay Power Corporation

Inspection Information - Office: Fort Lauderdale Area Office

 

Inspection Nr: 17429291
Report ID: 0418800
Date Opened: 10/24/1988

Site Address:
Montenay Power Corporation
6990 Nw 97th Ave.
Miami, FL 33178

Mailing Address:
P O Box 526430, Miami, FL 33152

Union Status: NonUnion

SIC:4953

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/19/1988

Emphasis:

Case Closed: 01/16/1989


Related Activity
Type Activity Nr Safety Health
Accident 360132864
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $560 $0 $0 $0 $0 $560
Current Penalty $560 $0 $0 $0 $0 $560
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 12/29/1988 01/01/1989 $560 $560 $0 -  

Investigation Summary

Investigation Nr: 14350045
Event: 10/20/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN ELECTRICAL FOREMAN AND A CREW OF FOUR OTHER EMPLOYEES WERE ATTEMPTING TO LOCATE A POSSIBLE GROUND FAULT IN A PROCESS TRANSFORMER IN A MOTOR CONTROL CENTER. THE CIRCUIT BREAKER INVOLVED HAD BEEN RACKED OUT SO THAT THE EMPLOYEES COULD CHECK THE INSIDE OF THE CUBICLE. HOWEVER, THE SUPPLY BUS WITHIN THE CUBICLE REMAINED ENERGIZED. WHILE THE FOREMAN WAS IN THE CUBICLE CONNECTING THE MEGGER WITH THE LOAD SIDE OF THE BUS, AN ACCIDENTAL CONTACT WITH THE ENERGIZED SUPPLY BUS CAUSED AN ELECTRIC ARC THROUGH THE MEGGER LEAD TO THE FOREMAN'S HAND. THE FOREMAN WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, BUSBAR, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 17429291 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.