Inspection: 15289200 - Weeks Construction Co

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 15289200
Report ID: 0453710
Date Opened: 06/10/1985

Site Address:
Weeks Construction Co
Hodge Rd Near Poole Rd
Knightdale, NC 27545

Mailing Address:
P O Box 1, Asheboro, NC 27201

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/18/1985

Emphasis:

Case Closed: 04/17/1987


Related Activity
Type Activity Nr Safety Health
Accident 360611859
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $420 $0 $0 $0 $0 $420
Current Penalty $420 $0 $0 $0 $0 $420
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260028 A 08/07/1985 08/10/1985 $420 $420 $0 09/04/1985 W - Empr Withdrew  

Investigation Summary

Investigation Nr: 14255624
Event: 06/06/1985
ELECTRIC SHOCK - VOLTAGE BACKFEED IN OVERHEAD LINE

AN EMPLOYEE WAS RECONNECTING A JUMPER WIRE THAT HAD PREVIOUSLY BEEN SEVERED TO ALLOW WORK TO BE PERFORMED ON ONE OF A SET OF THREE PHASE CONDUCTORS. THE FOREMAN AT THE SITE INFORMED THE EMPLOYEE THAT THE THREE PHASE CONDUCTORS HAD BEEN DEENERGIZED AT THE SWITCH POLE. AN INSULATING SLEEVE HAD BEEN PLACED ON THE ENERGIZED PORTION OF THE JUMPER WIRE. WHEN THE EMPLOYEE TOUCHED THE PORTION OF THE JUMPER WIRE THAT WAS CONNECTED TO THE "DEENERGIZED" CONDUCTOR, HE WAS ELECTROCUTED. ONLY TWO OF THE THREE PHASES WERE DISCONNECTED AT THE SWITCH POLE. THE LINE THE EMPLOYEE CONTACTED WAS ENERGIZED BY VOLTAGE BACKFEED THROUGH A BANK OF TRANSFORMERS AND SOME MOTORS IN A NEARBY STORE.

Keywords: VOLTAGE BACKFEED, OVERHEAD POWER LINE, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 15289200 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.