Powered by GoogleTranslate

Inspection Detail

Inspection: 14892699 - Peoples Electric Company

Inspection Information - Office: Minnesota Department Of Labor And Industry

 

Inspection Nr: 14892699
Report ID: 0552700
Date Opened: 12/06/1984

Site Address:
Peoples Electric Company
1510 14th St Nw (John Marshall High School)
Rochester, MN 55901

Mailing Address:
277 E Fillmore Avenue, St Paul, MN 55107

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/06/1984

Emphasis:

Case Closed: 12/18/1984


Related Activity
Type Activity Nr Safety Health
Accident 360589055

Investigation Summary

Investigation Nr: 14448047
Event: 12/05/1984
ELECTRIC SHOCK - CONTACT WITH EXPOSED LIVE PARTS

TWO LARGE ELECTRIC TRANSFORMERS AT A HIGH SCHOOL HAD BEEN REPLACED IN THE SUMMER OF 1984, BECAUSE THE FORMER ONES WERE CONTAMINATED WITH PCB. THE HIGH VOLTAGE CABLE BETWEEN THE NORTH AND SOUTH TRANSFORMERS HAD BEEN CHANGED ON DECEMBER 2, 1984. BECAUSE ELECTRIC BALLASTS AND OTHER ELECTRIC EQUIPMENT IN THIS SCHOOL WERE BURNING OUT, THE ELECTRIC UTILITY COMPANY WAS CALLED TO INVESTIGATE. THE UTILITY COMPANY MEASURED THE SECONDARY VOLTAGE TO BE BETWEEN 126 AND 129 VOLTS, AND THIS HIGHER THAN NORMAL VOLTAGE WAS CAUSING THE PROBLEM. THE GENERAL FOREMAN OF AN ELECTRICAL CONTRACTING COMPANY ARRIVED ON DECEMBER 5 TO CHANGE THE TAPS IN THE NORTH TRANSFORMER. HE ARRIVED AROUND 6:30 AM. THE MAIN DISCONNECT FOR THIS TRANSFORMER WAS OPENED AND THE LOW VOLTAGE DISCONNECT WAS ALSO OPENED. THE PANEL OVER THE TAPS WAS REMOVED, AND THE FOREMAN CHANGED THE TAPS TO A DIFFERENT POSITION TO LOWER THE VOLTAGE. THE POWER WAS RESTORED. A CUSTODIAL ENGINEER WAS HOLDING A LIGHT FOR THE FOREMAN. WHEN THE POWER WAS RESTORED, THE FIRE ALARM SYSTEM WAS ACITVATED. THIS WAS NORMAL. THE CUSTODIAL ENGINEER WENT TO THE OFFICE TO SHUT OFF THE FIRE ALARM. A SUPERVISOR ARRIVED FOR WORK AROUND 6:55 AM. HE MET THE CUSTODIAL ENGINEER IN THE HALLWAY. BOTH MEN WENT TO THE NORTH TRANSFORMER ROOM AND FOUND THE FOREMAN LYING INSIDE THE METAL ENCLOSURE, NEAR THE SOUTH END, WHERE HE HAD CHANGED THE TRANSFORMER TAPS. HE WAS SEMI-CONSCIOUS. HE LATER DIED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, ELECTRICAL WORK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 14892699 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.