Inspection Detail
Case Status: CLOSED |
Inspection Information - Office: Nc Charlotte | ||||
---|---|---|---|---|
Nr: 1475504.015 | Report ID: 0453730 | Open Date: 05/15/2020 | ||
Town Of Maiden | ||||
24 Salem Church Road Maiden, NC 28650 | Union Status: NonUnion | |||
SIC: 9631/Regulation and Administration of Communications, Electric, Gas, and Other Utilities | ||||
NAICS: 926130/ Regulation and Administration of Communications, Electric, Gas, and Other Utilities | ||||
Mailing: 19 N. Main Avenue, Maiden, NC 28650 | ||||
Inspection Type: | Fat/Cat | |||
Scope: | Partial | Advanced Notice: | N | |
Ownership: | LocalGovt | |||
Safety/Health: | Health | Close Conference: | 09/16/2020 | |
Close Case: | 01/15/2021 | |||
Related Activity: | Type | ID | Safety | Health |
Accident | 1590528 |
Case Status: CLOSED |
Violation Summary | ||||||
---|---|---|---|---|---|---|
Serious | Willful | Repeat | Other | Unclass | Total | |
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $7,000 | $0 | $0 | $0 | $0 | $7,000 |
Current Penalty | $5,250 | $0 | $0 | $0 | $0 | $5,250 |
FTA Amount | $0 | $0 | $0 | $0 | $0 | $0 |
Violation Items | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
# | ID | Type | Standard | Issuance | Abate | Curr$ | Init$ | Fta$ | Contest | LastEvent | |
1. | 01001 | Serious | 19260960 C01 III | 09/18/2020 | 09/28/2020 | $2,625 | $3,500 | $0 | I - Informal Settlement | ||
2. | 01002 | Serious | 19260960 F | 09/18/2020 | 09/28/2020 | $2,625 | $3,500 | $0 | I - Informal Settlement |
Accident Investigation Summary | ||||||
Summary Nr: 127626.015 | Event: 05/15/2020 | Employee Is Killed By Electrocution | ||||
At 5:55 p.m. on May 15, 2020, Employee # 1, an electric lineman, was performing a gloved, live-line transfer of a three-phase electric distribution service to a new, taller pole. After completing the transfer of each of the three phases, he began installing the phase jumpers for each of the three phases. He completed the field phase jumper installation. While installing the center phase jumper, his left shoulder blade area contacted an exposed energized part (deadend clamp or "shoe") while he had a conductive object (spare jumper wire) in the aerial bucket with him, leaning against his left thigh. The electricity went from the energized shoe, into his body at his left shoulder, through his body, and exited at his left thigh. Once the ground crew realized that Employee # 1 was not answering their calls, they performed a pole-top rescue and brought him down from his work area. He was found to be unresponsive. He was killed by electrocution. | ||||||
Keywords: shoulder, electrocuted, live-line tool, installing, glove, electrical work, bucket , unresponsive, electrical, electric shock, energized, thigh | ||||||
Inspection | Degree | Nature | Occupation | |||
---|---|---|---|---|---|---|
1 | 1475504.015 | Fatality | Electric Shock | Occupation not reported |