Inspection Detail
Inspection: 1468775.015 - Delaware City Refining Company, Llc
Inspection Information - Office: Wilmington Area Office
Site Address:
Delaware City Refining Company, Llc
4550 Wrangle Hill Road
Delaware City, DE 19706
Mailing Address:
4550 Wrangle Hill Road, Delaware City, DE 19706
Union Status: Union
SIC:
NAICS: 324110/Petroleum Refineries
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Health
Close Conference: 09/11/2020
Emphasis: N:Chemnep
Case Closed: 01/14/2025
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 1551884 | Yes | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 10 | 2 | 12 | |||
Current Violations | 10 | 10 | ||||
Initial Penalty | $132,049 | $269,874 | $0 | $0 | $0 | $401,923 |
Current Penalty | $401,923 | $0 | $0 | $0 | $0 | $401,923 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100119 D03 II | 09/11/2020 | 10/29/2020 | $17,982 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
2. | 01002 | Serious | 19100119 E03 III | 09/11/2020 | 10/29/2020 | $15,994 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
3. | 01003 | Serious | 19100119 E03 V | 09/11/2020 | 10/29/2020 | $0 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | Citation has been deleted. |
4. | 01004 | Serious | 19100119 E03 VI | 09/11/2020 | 10/29/2020 | $0 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | Citation has been deleted. |
5. | 01005 | Serious | 19100119 F01 I D | 09/11/2020 | 10/29/2020 | $15,994 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
6. | 01006 | Serious | 19100119 F01 II A | 09/11/2020 | 10/29/2020 | $15,994 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
7. | 01007 | Serious | 19100119 G01 I | 09/11/2020 | 10/29/2020 | $15,994 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
8. | 01008 | Serious | 19100119 N | 09/11/2020 | 10/29/2020 | $15,994 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
9. | 01009A | Serious | 19100120 Q06 I | 09/11/2020 | 10/29/2020 | $15,994 | $13,494 | $0 | 10/02/2020 | F - Formal Settlement | |
10. | 01009B | Serious | 19100120 Q06 II | 09/11/2020 | 10/29/2020 | $0 | $0 | $0 | 10/02/2020 | F - Formal Settlement | |
11. | 01009C | Serious | 19100120 Q08 I | 09/11/2020 | 10/29/2020 | $0 | $0 | $0 | 10/02/2020 | F - Formal Settlement | |
12. | 01010 | Serious | 19100132 D01 I | 09/11/2020 | 10/07/2020 | $13,103 | $10,603 | $0 | 10/02/2020 | F - Formal Settlement | |
13. | 02001 | Serious | 19100119 E05 | 09/11/2020 | 10/29/2020 | $137,437 | $134,937 | $0 | 10/02/2020 | F - Formal Settlement | |
14. | 02002A | Serious | 19100119 J02 | 09/11/2020 | 10/29/2020 | $137,437 | $134,937 | $0 | 10/02/2020 | F - Formal Settlement | |
15. | 02002B | Serious | 19100119 J04 I | 09/11/2020 | 10/29/2020 | $0 | $0 | $0 | 10/02/2020 | F - Formal Settlement | |
16. | 02002C | Willful | 19100119 J04 II | 09/11/2020 | 10/29/2020 | $0 | $0 | $0 | 10/02/2020 | F - Formal Settlement | Citation has been deleted. |
Investigation Summary
At 1:30 p.m. on March 11, 2020, two employees were responding to a heater-temperature alarm transmitted to the control room from a heater tube thermocouple. Initially, just prior to activating a shutdown response, multiple operators reported a more than usual smoke volume emitting from the smokestack for this heater. It was reported that an even greater smoke volume emitted. Then, there was a sudden deflagration. The two employees, who at this time were responding to the heater-temperature alarm in the field and positioned right next to the heater peering into the heater's port holes, were thrown by the blast pressure, sustaining serious burn injuries from the fire. The direct equipment cause of this fire was due to the failure of a specific heater tube located in the convection section of the heater, the same tube, tube #66, that had failed in the past. The heater tube ruptured, spewing flammable distillates into the open space within the active, flaming heater box that ignited, erupting into an uncontained fire, eventually contained, and then extinguished by DCRC's fire brigade. One employee had serious burns to the face, neck, back and one hand; the other employee had serious burns to the face and neck. Both employees were hospitalized.
Keywords: Alarm, Back, Blasting, Burn, Face, Fire, Fire Brigade, Flammable Liquid, Flammable Vapors, Hand, Heater, Ignite, Neck, Operator, Refinery, Smoke
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1468775.015 | 31 | M | Hospitalized injury | Chemical technicians | |
2 | 1468775.015 | 45 | M | Hospitalized injury | Chemical technicians |