Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 14631121 - Hegemann Electric Inc

Inspection Information - Office: Arizona Phoenix Sfty

Nr: 14631121Report ID: 0950411Open Date: 06/06/1984

Hegemann Electric Inc
180 West Broadway
Tucson, AZ 85701
Union Status: NonUnion
SIC: 1731/Electrical Work
Mailing: 1665 East 18th St Suite 119, Tucson, AZ 85719

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:06/29/1984
Planning Guide: Safety-Construction Close Case:06/29/1984

Related Activity:TypeIDSafetyHealth
 Accident360578447    

Accident Investigation Summary
Summary Nr: 14565352Event: 06/05/1984Burn - Electrical Fault In Switchboard
Two employees were installing new compression-type connectors on conductors on the load side of an electrical switchboard. The switchboard contained a three-phase circuit operating at 480 volts (277 volts to ground), 1200 amperes. The fuses for the circuit had been removed, deenergizing the load side of the circuit. Employee #2 was tightening one of the connectors when the supply side of the circuit faulted to ground or from one phase to another. (Employee #1 was standing beside employee #2, in front of the switchboard.) No defects that could have caused the fault were found in the switchboard. A pair of pliers and a screwdriver were lying in the bottom of the switchboard. It was theorized that employee #1 may have attempted to remove them while employee #2 was installing the connectors and, in the process, may have accidentally struck the uninsulated portion of the circuit on the energized side. Both employees received second- and third-degree burns from the ensuing electric arc and were hospitalized.
Keywords: burn, clothing, e gi ii, electric arc, electrical, electrician, electrical work, lockout, electrical fault, hand tool
Inspection Degree Nature Occupation
1 14631121 Hospitalized injury Burn/Scald(Heat) Electricians
2 14631121 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.