Powered by GoogleTranslate

Inspection Detail

Inspection: 1427285 - Temple Associates Inc

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 1427285
Report ID: 0626600
Date Opened: 09/20/1984

Site Address:
Temple Associates Inc
700 North Temple Dr
Diboll, TX 75941

Mailing Address:
Po Box 730, Diboll, TX 75941

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/21/1984

Emphasis:

Case Closed: 11/13/1984


Related Activity
Type Activity Nr Safety Health
Accident 360548788
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $560 $0 $0 $0 $0 $560
Current Penalty $560 $0 $0 $0 $0 $560
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 E01 II 10/02/1984 10/05/1984 $560 $560 $0 A - Amendment  

Investigation Summary

Investigation Nr: 14237143
Event: 09/19/1984
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU TOOL CORD

WORKING FROM AN INSULATED BUCKET OF AN AERIAL LIFT, AN EMPLOYEE WAS ABOUT TO DRILL A HOLE IN A UTILITY POLE. HE WAS USING A BLACK AND DECKER PORTABLE ELECTRIC DRILL, WHICH HE HAD RAISED TO THE AERIAL LIFT BUCKET BY PULL ROPE. HE WAS WEARING A PAIR OF LEATHER GLOVES, RATHER THAN THE RUBBER INSULATING GLOVES THAT WERE IN THE BUCKET WITH HIM. THE DRILL WAS POWERED BY A VEHICLE-MOUNTED GENERATOR ON THE AERIAL LIFT TRUCK, AND THE CORD WAS RUN FROM THE GENERATOR (WITH THE CORD ON THE GROUND) UP TO THE BUCKET. AS THE EMPLOYEE MOVED THE DRILL INTO POSITION, THE CORD CONTACTED AN ENERGIZED 14,400-VOLT OVERHEAD POWER LINE. THE CURRENT PASSED THROUGH THE CORD AND MELTED IT AND THE OVERHEAD LINE. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CORD, ELECTRIC DRILL, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1427285 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close