Powered by GoogleTranslate

Inspection Detail

Inspection: 1392471 - Bowie Cass Electric Co Op Inc

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 1392471
Report ID: 0626300
Date Opened: 11/21/1984

Site Address:
Bowie Cass Electric Co Op Inc
Approx 6 Miles Se
Douglassville, TX 75560

Mailing Address:
P O Box 47, Douglassville, TX 75560

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 11/27/1984

Emphasis:

Case Closed: 09/30/1985


Related Activity
Type Activity Nr Safety Health
Accident 360640023
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations
Initial Penalty $560 $0 $0 $0 $0 $560
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260400 C01 12/13/1984 12/26/1984 $560 $560 $0 01/14/1985 J - ALJ Decision Citation has been deleted.
2. 01001B Serious 19260955 C05 12/13/1984 12/26/1984 $0 $0 $0 A - Amendment Citation has been deleted.
3. 02001 Other 19040002 A 12/13/1984 12/26/1984 $0 $0 $0 01/14/1985 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 14399422
Event: 11/19/1984
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

TWO EMPLOYEES WERE RECONNECTING THE LINE AND NEUTRAL CONDUCTORS LEADING FROM A UTILITY POLE TO A VACANT HOUSE. ONE EMPLOYEE, WHO WAS ON THE GROUND, USED A HAND LINE TO PULL THE NEUTRAL CONDUCTOR UP TO THE OTHER EMPLOYEE, WHO WAS ON THE POLE. THE EMPLOYEE ON THE POLE WAS WEARING INSULATING GLOVES AND HAD THE NEUTRAL CONDUCTOR IN HIS HAND WHEN IT CONTACTED A 7200-VOLT OVERHEAD POWER LINE ON TOP OF THE POLE. THE LINE CONDUCTOR FROM THE VACANT HOUSE WAS LYING ON A BARBED WIRE ON THE GROUND, AND THE EMPLOYEE ON THE GROUND WAS STANDING ON THE BARBED WIRE. CURRRENT FROM THE ENERGIZED LINE WAS CONDUCTED THROUGH THE NEUTRAL TO THE LINE CONDUCTOR AT THE WEATHER HEAD ON THE HOUSE. THIS LINE CONDUCTED CURRENT TO THE BARBED WIRE, ENERGIZING IT AND ELECTROCUTING THE EMPLOYEE STANDING ON IT.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1392471 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close