Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail



Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 15 15
Current Violations 15 15
Initial Penalty $0 $0 $0 $0 $1,500,000 $1,500,000
Current Penalty $0 $0 $0 $0 $1,500,000 $1,500,000
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  2. 01002 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  3. 01003 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  4. 01004 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  5. 01005 Unclass 19100269 C 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  6. 01006 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  7. 01007 Unclass 19100269 D02 III 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  8. 01008 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  9. 01009 Unclass 19100307 B 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  10. 01010 Unclass 4081141102 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  11. 01011 Unclass 40811441 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  12. 01012 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  13. 01013 Unclass 19100269 A02 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  14. 01014 Unclass 19101200 G01 09/02/1999 10/12/1999 $100,000 $100,000 $0 -
  15. 01015 Unclass 40801011 A 09/02/1999 10/12/1999 $100,000 $100,000 $0 -

Accident Investigation Summary
Summary Nr: 201390945 Event: 02/01/1999Six Employees Killed In Explosion
Six employees were taking a boiler off-line for maintenance. A natural gas valve was inadvertently left open. When a secondary butterfly valve was opened for purging, gas entered the unfired boiler which was still hot. This resulted in an explosion in the boiler and that explosion caused secondary explosions from coal dust that had accumulated on building and equipment surfaces. All six employees were killed in the explosion.
Keywords: heat, coal dust, boiler, natural gas, explosion, elec utility work
Inspection Degree Nature Occupation
1 127242105 Fatality Other Occupation not reported
2 127242105 Fatality Other Occupation not reported
3 127242105 Fatality Other Occupation not reported
4 127242105 Fatality Other Occupation not reported
5 127242105 Fatality Other Occupation not reported
6 127242105 Fatality Other Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.