Powered by GoogleTranslate

Inspection Detail

Inspection: 126127588 - Abm Engineering Services

Inspection Information - Office: Monrovia District Office

 

Inspection Nr: 126127588
Report ID: 0950644
Date Opened: 12/10/1998

Site Address:
Abm Engineering Services
505 N. Brand Blvd.
Glendale, CA 91203

Mailing Address:
5300 S. Eastern Ave., #100, Los Angeles, CA 90040

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/27/1999

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/06/2000


Related Activity
Type Activity Nr Safety Health
Accident 362623175
Accident 362623183
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $6,250 $0 $0 $0 $0 $6,250
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 23200002 A 05/28/1999 06/30/1999 $5,000 $6,250 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201792017
Event: 12/10/1998
Burn - Electrical Fault in Disconnect

The chief operating engineer for an office building was investigating the cause of a lighting failure on the seventh floor of the building. He found two tripped circuit breakers in a 277-volt panelboard. He closed the two circuit breakers. A second complaint about lights out on the seventh floor led the employee to investigate further. He removed the front cover of the panelboard and found that one phase bus was not energized. He traced this phase back to its source, a 480/277-volt, 150-ampere, three-phase disconnect switch. He used test equipment to locate a blown fuse on one phase. Using a nonmetallic fuse puller, he began to pull the open fuse while it remained energized. He did not deenergize the fuse to avoid disrupting power while he retrieved a replacement on another floor. The top of the fuse came out easily, but the bottom, or line side, of the fuse was stuck. He pulled on the fuse pullers with both hands. The fuse broke loose and caused an electrical fault. The ensuing electric arc burned the employee. He was hospitalized for 17 days for second- and third-degree burns to his hands, arms, face, and chest.

Keywords: BURN, CLOTHING, FUSE, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126127588 Hospitalized injury Electric Shock Stationary engineers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.