Inspection: 126078989 - Lawson Electric

Inspection Information - Office: Monrovia District Office

 

Inspection Nr: 126078989
Report ID: 0950644
Date Opened: 09/29/1999

Site Address:
Lawson Electric
1800 W Holt Ave
Pomona, CA 91766

Mailing Address:
675 H N. Eckhoff St., Orange, CA 92868

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/03/1999

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 06/18/2001


Related Activity
Type Activity Nr Safety Health
Accident 362547259
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 2 3
Initial Penalty $5,500 $0 $0 $165 $0 $5,665
Current Penalty $3,000 $0 $0 $85 $0 $3,085
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 12/03/1999 01/04/2000 $85 $165 $0 12/16/1999 F - Formal Settlement  
2. 02001 Other 1670 A 12/03/1999 01/04/2000 $0 $1,125 $0 12/16/1999 F - Formal Settlement  
3. 03001 Serious 23200004 A 12/03/1999 01/04/2000 $3,000 $4,375 $0 12/16/1999 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201792439
Event: 09/29/1999
Electric Shock - Contact with Energized Conductor

Three employees of an electrical contractor were installing 277-volt florescent lighting fixtures on an existing circuit. Employee #1 was a nonjourneyman electrician with 3 years and 9 months of electrical experience. (He was enrolled in a recognized craft training program.) He and one of the other two employees climbed onto an open cable tray so that they could open the top of an enclosed cable tray to gain access to the lighting circuit conductors. The cable tray with the lighting circuit was more than 3.4 meters above a screen-install platform. The employees were not using fall arrest equipment. After assisting Employee #1 in removing the cover from the cable tray, the second employee departed, but noticed that the fluorescent lights were on. Employee #1 cut the two lighting circuit conductors without apparent incident. However, as he was stripping the energized conductor, he received an electric shock, which caused him to hit his head on a disconnect handle directly above him and fall through the suspended ceiling to the screen-install platform. He was electrocuted.

Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC SHOCK, FALL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126078989 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.