Powered by GoogleTranslate

Inspection Detail

Inspection: 126059245 - Abm Engineering

Inspection Information - Office: Los Angeles District Office

 

Inspection Nr: 126059245
Report ID: 0950641
Date Opened: 01/06/2003

Site Address:
Abm Engineering
4640 Admiralty Wy.
Marina Del Rey, CA 90292

Mailing Address:
300 S. Eastern Ave., Ste. #100, Los Angeles, CA 90040

Union Status: NonUnion

SIC:6531

NAICS: 531312/Nonresidential Property Managers


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/13/2003

Emphasis:

Case Closed: 06/16/2003


Related Activity
Type Activity Nr Safety Health
Accident 362582108
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $185 $0 $185
Current Penalty $0 $0 $0 $185 $0 $185
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 B02 06/13/2003 06/18/2003 $185 $185 $0 -  

Investigation Summary

Investigation Nr: 201164548
Event: 12/15/2002
Employee Is Injured in Arc Blast

At approximately 11:00 a.m. on December 15, 2002, Employee #1, a building maintenance engineer, was tightening the fuse attachments in a 440-volt motor control panel. There was a switch in the panel, which deenergized the load side of the circuit, and on the far left of the panel was the supply side, which remained energized. This was the fifth panel that Employee #1 had serviced that day. He had a volt tester with him and had verified that there was zero voltage on the load side, but proceeded to put a socket wrench on a bolt on the left side. When he touched the bolt, an arc blast occurred that burned both of his hands and caused temporary blindness, and subsequent memory loss. He was hospitalized for his injuries.

Keywords: BURN, ELECTRIC MOTOR, FUSE, ELECTRIC ARC, PANEL, ELECTRICIAN, ELECTRIC METER, BOLT, ELECTRIC SHOCK, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 126059245 Hospitalized injury Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.