Inspection: 125908061 - Champ Steel

Inspection Information - Office: Ca Santa Ana District Office

Nr: 125908061Report ID: 0950631Open Date: 07/09/1997

Champ Steel
5301 Bolsa Ave
Huntington Beach, CA 92647
Union Status: Union
SIC: 3721/Aircraft
Mailing: 633 E Young St, Santa Ana, CA 92705

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:09/22/1997
Planning Guide: Safety-Manufacturing Close Case:05/09/2003

Related Activity:TypeIDSafetyHealth
 Accident362216384    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 2 3
Initial Penalty $6,500 $0 $0 $600 $0 $7,100
Current Penalty $0 $0 $0 $750 $0 $750
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 2944 H01 B 09/26/1997 10/19/1997 $600 $600 $0 -
  2. 02001 Other 2811 09/26/1997 10/19/1997 $150 $5,000 $0 F - Formal Settlement
  3. 03001 Serious 2940 B 09/26/1997 10/19/1997 $0 $1,500 $0 D - Govt Dismissed

Accident Investigation Summary
Summary Nr: 201140373Event: 04/26/1997Burn - Voltage Tester Failed
An electrician was working in a substation. He was performing preventive maintenance, cleaning the low-voltage (480-volt) side of a transformer. The electrician tried to test the incoming high-voltage (12-kilovolt) conductors with a tester rated for 600 volts maximum. The tester failed, and the ensuing electric arc burned the employee. He sustained second- and third-degree burns to both his hands and to his face. He was hospitalized for his injuries.
Keywords: burn, electric arc, electrical, electrician, equipment failure, test equipment, e ptd, elec utility work, electrical fault
Inspection Degree Nature Occupation
1 125908061 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.