Powered by GoogleTranslate

Inspection Detail

Inspection: 125867598 - Martinez Refining Company

Inspection Information - Office: American Canyon District Office

 

Inspection Nr: 125867598
Report ID: 0950622
Date Opened: 05/18/1998

Site Address:
Martinez Refining Company
1800 Marina Vista
Martinez, CA 94553

Mailing Address:
Po Box 711, Martinez, CA 94553

Union Status: Union

SIC:2911

NAICS: 324110/Petroleum Refineries


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/20/1998

Emphasis:

Case Closed: 10/01/1998


Related Activity
Type Activity Nr Safety Health
Accident 362083602
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $0 $0 $525 $0 $525
Current Penalty $0 $0 $0 $525 $0 $525
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 6778 08/04/1998 08/04/1998 $350 $350 $0 -  
2. 01002 Other 6846 C 08/04/1998 08/04/1998 $175 $175 $0 -  

Investigation Summary

Investigation Nr: 201481009
Event: 05/15/1998
EMPLOYEE INJURED WHEN BURNED BY ESCAPING STEAM

Employee #1, a boiler operator, sustained first and second-degree burns when 650 psig steam and 495 degrees Fahrenheit hot water erupted out of an atmospheric vent located 8-to-9 inches above his work location on the deck. Employee #1 was able to remove himself from the upper deck; however, his escape was hampered by the presence of piping and appurtenances. Employee #1 had "cracked" open a 2-inch vent valve which had been leaking. Over a period of time the steam leaking by the valve had condensed in the 4-inch vent line and it combined somewhat violently with the 650 psig steam once the operator opened the vent valve. The resulting discharge from the atmospheric vent was not mitigated by a diverter on the vent or by the presence of a protective canopy above Employee #1's work location at the valve. Employee #1 was hospitalized for three days; however, skin grafts were not necessary. Employee #1 has since returned to full duties.

Keywords: BURN, VENTING, BOILER, STEAM, VALVE, SKIN, ACCIDENTAL DISCHARGE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125867598 Hospitalized injury Burn/Scald(Heat) Power plant operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.