Powered by GoogleTranslate

Inspection Detail

Inspection: 125493106 - Decker Electric

Inspection Information - Office: San Francisco District Office

 

Inspection Nr: 125493106
Report ID: 0950611
Date Opened: 05/08/2000

Site Address:
Decker Electric
600 Battery Street
San Francisco, CA 94111

Mailing Address:
1282 Folsom St., San Francisco, CA 94103

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/23/2000

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/26/2001


Related Activity
Type Activity Nr Safety Health
Accident 361568876
Accident 361571201
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 1 2 3
Initial Penalty $18,000 $0 $0 $450 $0 $18,450
Current Penalty $2,700 $0 $0 $450 $0 $3,150
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 07/18/2000 07/21/2000 $300 $300 $0 F - Formal Settlement  
2. 01002 Other 1509 A 07/18/2000 08/20/2000 $150 $150 $0 F - Formal Settlement  
3. 02001 Serious 23200004 A 07/18/2000 07/24/2000 $2,700 $18,000 $0 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170205967
Event: 04/15/2000
ELECTRIC SHOCK - CONTACT WITH ENERGIZED CONDUCTOR

An apprentice electrician had been working for his employer for 7 months. He was assigned by his supervisor to work on a 277-volt ceiling lighting fixture. He checked the voltage and his testing indicated that the circuit was deenergized. However, as he was pulling out the conductors, he got an electric shock. He asked a supervisor if the circuit had been deenergized, and the supervisor responded that it had been. When he checked the conductors with his voltmeter, he got a no-voltage reading. He pulled out the conductors and, when he cut through them, received another electric shock and a burn on a finger on his right hand. He was hospitalized for his injuries. Employees of another contractor were working at the panelboard supplying the lighting circuit. (Two days earlier, the injured employee had been trimming conductors for a transformer when he received an electric shock. This electric shock had been caused by backfeed on the neutral from another circuit.)

Keywords: BURN, LIGHTING CIRCUIT, E GI IV, ELECTRICAL, FINGER, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 125493106 Hospitalized injury Burn/Scald(Heat) Electricians' apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.