Powered by GoogleTranslate

Inspection Detail

Inspection: 124616624 - Icg Electric Inc

Inspection Information - Office: Utah Division Of Occupational Safety And Health

 

Inspection Nr: 124616624
Report ID: 0854910
Date Opened: 06/14/1993

Site Address:
Icg Electric Inc
6353 North 2150 West
Smithfield, UT 84335

Mailing Address:
2712 Industrial Drive, Ogden, UT 84401

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/01/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 07/30/1993


Related Activity
Type Activity Nr Safety Health
Accident 360291975
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,125 $0 $0 $0 $0 $1,125
Current Penalty $1,125 $0 $0 $0 $0 $1,125
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A03 07/26/1993 07/30/1993 $1,125 $1,125 $0 -  

Investigation Summary

Investigation Nr: 170560973
Event: 06/10/1993
ELECTRIC SHOCK & FALL - DIRECT CONTACT WITH ENERGIZED PARTS

Three employees (a journeyman electrician and two apprentice electricians) of an electrical contractor were working in a mechanical hallway. The journeyman electrician was sitting on an insulated steam pipe located about 8 feet above the floor. The working space was limited because of other (HVAC, condensation, steam, and compressed air) pipes hanging at about the same level. The electrician was working on a junction box mounted on the wall. The junction box contained conductors for an energized 277-volt, 20-ampere lighting circuit. He was connecting wiring for new fixtures to the existing wiring in the box. The hallway was hot because of the steam pipes, and the electrician was sweating heavily. He asked one of the apprentices to hand him a screwdriver. As the apprentice did this, he heard a sizzling sound. He looked up and saw the electrician in contact with energized parts of the circuit. The apprentice twice tried to push the electrician away, but was knocked down both times. The apprentice then went to a circuit breaker cabinet in the hallway to deenergize the circuit. None of those circuit breakers controlled the lighting circuit, however, so he went through a door to an adjacent room. The workers in that room were employed by a dairy. One of them called for emergency medical services, and the others went into the hallway. They used a board to separate the injured employee from the energized parts and administered cardio-pulmonary resuscitation until the emergency medical services arrived. In spite of these efforts, the electrician died of electrocution.

Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 124616624 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close