Powered by GoogleTranslate

Inspection Detail

Inspection: 123255036 - Silas Bolef Company

Inspection Information - Office: Allentown Area Office

 

Inspection Nr: 123255036
Report ID: 0317900
Date Opened: 04/21/1995

Site Address:
Silas Bolef Company
Lonza Inc., Aka Smithkline Beecham 900 River Road
Norristown, PA 19428

Mailing Address:
Forrest Avenue & Lafayette Street, Norristown, PA 19428

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Complaint

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/19/1995

Emphasis:

Case Closed: 06/21/1995


Related Activity
Type Activity Nr Safety Health
Complaint 75205880 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $6,000 $0 $0 $0 $0 $6,000
Current Penalty $3,300 $0 $0 $0 $0 $3,300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 06/06/1995 06/09/1995 $1,800 $3,000 $0 I - Informal Settlement  
2. 01002 Serious 19260095 A 06/06/1995 06/09/1995 $1,500 $3,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 170340863
Event: 04/21/1995
BURN - ELECTRICAL FAULT IN ELECTRIC SWITCH

An employee (employee #2) was removing a grounding strap from a 4160-volt air switch. The uninsulated handle of the strap contacted the line side of the switch stab, creating an electrical fault. The employee was burned over 50 to 70 percent of his body by the ensuing electric arc. Employee #1, who was working next to him, was also burned by the electric arc and had his clothing ignite. Three other employees sustained burns when they tried to extinguish the burning clothing. The two employees burned by the arc and one of the other employees were hospitalized for their injuries.

Keywords: ELECTRIC ARC, PROTECTIVE GROUNDING, ELECTRICAL, BURN, CLOTHING, ELECTRICIAN, ELECTRICAL FAULT, E GI II, ELECTRIC SWITCH, ELECTRICAL WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 123255036 Hospitalized injury Burn/Scald(Heat) Electricians
2 123255036 Hospitalized injury Burn/Scald(Heat) Electricians
3 123255036 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close