Inspection: 122280233 - Lyons Electric Co. Inc.

Inspection Information - Office: Chicago South Area Office

 

Inspection Nr: 122280233
Report ID: 0521700
Date Opened: 04/17/1996

Site Address:
Lyons Electric Co. Inc.
Cummins St. Drawbridge & 130th St. & Torrence Ave.
Chicago, IL 60633

Mailing Address:
4225 Lawndale Ave., Lyons, IL 60534

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 07/24/1996

Emphasis:

Case Closed: 10/25/1996


Related Activity
Type Activity Nr Safety Health
Accident 360427371
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,500 $0 $0 $0 $0 $2,500
Current Penalty $1,500 $0 $0 $0 $0 $1,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100333 A 08/13/1996 10/22/1996 $1,500 $2,500 $0 I - Informal Settlement  
2. 01001B Serious 19100335 A01 I 08/13/1996 10/22/1996 $0 $0 $0 -  
3. 01001C Serious 19100335 A02 I 08/13/1996 10/22/1996 $0 $0 $0 -  
4. 01001D Serious 19100335 A02 II 08/13/1996 10/22/1996 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 200030096
Event: 01/25/1996
BURN - ELECTRICAL FAULT IN PANELBOARD

An electrician was working on a Westinghouse 480-volt main distribution panelboard, in preparation for the installation of a transfer switch. The employee was not wearing a face shield, nor was he using electrical protective equipment. The employee apparently caused an electrical fault. The ensuing electric arc critically burned the employee on his chest, face, and arm. He died of his injuries on April 14, 1996, almost 3 months after the accident.

Keywords: BURN, CLOTHING, E GI II, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122280233 Fatality Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.