Powered by GoogleTranslate

Inspection Detail

Inspection: 122209281 - Wisconsin Electric Power Company

Inspection Information - Office: Milwaukee Area Office

 

Inspection Nr: 122209281
Report ID: 0523400
Date Opened: 02/12/1995

Site Address:
Wisconsin Electric Power Company
8000 95th Street
Pleasant Prairie, WI 53158

Mailing Address:
333 Everett Street, Milwaukee, WI 53203

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/05/1995

Emphasis:

Case Closed: 08/23/1995


Related Activity
Type Activity Nr Safety Health
Accident 360407464

Investigation Summary

Investigation Nr: 14367643
Event: 02/12/1995
BURN - STEAM PIPE RUPTURE

A feed water inlet header pipe supplying a boiler at an electric power generating station ruptured at elevation 227. (The elevations noted in the abstract are in reference to Lake Michigan which is at a relative elevation of 0. Ground elevation at the plant was 105.) The pipe was under 1875 psi, and the contained steam was at 426 degrees Fahrenheit at the time of release. The rupture flooded the upper portion of a generation unit at the generating plant. Two supervisory employees, who were performing a routine inspection, were trapped in the area at elevation 303. One of the employees died at the scene; he had burns over 90 percent of his body. The second employee suffered burns over 60 percent of his body. He was hospitalized in critical condition. (A technical team was to conduct a failure analysis, including metallurgical evaluation of the 15-year-old pipe, after the accident. The employer's quality assurance program for determining serviceability did not include this external boiler piping system as it was not deemed a high-risk area.)

Keywords: BURN, STEAM LINE, INADEQUATE MAINT, BOILER, STEAM, ELEC UTILITY WORK, MECH MALFUNCTION

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122209281 Fatality Burn/Scald(Heat) Power plant operators
2 122209281 Fatality Burn/Scald(Heat) Power plant operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.