Powered by GoogleTranslate

Inspection Detail

Inspection: 122136013 - Duke Power Company

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 122136013
Report ID: 0453710
Date Opened: 07/20/1993

Site Address:
Duke Power Company
Centre 311
Winston-Salem, NC 27101

Mailing Address:
422 South Church Street, Charlotte, NC 28242

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/25/1993

Emphasis:

Case Closed: 03/21/1996


Related Activity
Type Activity Nr Safety Health
Accident 360491971
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 2 1 3
Initial Penalty $15,500 $0 $0 $0 $0 $15,500
Current Penalty $5,250 $0 $0 $0 $0 $5,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 01/19/1994 01/25/1994 $0 $7,000 $0 02/04/1994 J - ALJ Decision Citation has been deleted.
2. 01001B Serious 19260955 A03 01/19/1994 01/24/1994 $5,250 $0 $0 02/04/1994 J - ALJ Decision  
3. 01002A Other 19260021 B02 01/19/1994 01/29/1994 $0 $0 $0 02/04/1994 Q - National Office Adjustment  
4. 01002B Other 19100184 I09 III 01/19/1994 01/25/1994 $0 $0 $0 02/04/1994 Y - State Decision  
5. 01002C Other 19260251 E01 01/19/1994 01/25/1994 $0 $0 $0 02/04/1994 Y - State Decision  
6. 01003 Serious 19260550 A16 01/19/1994 02/21/1994 $0 $1,500 $0 02/04/1994 Y - State Decision Citation has been deleted.
7. 01004 Serious 19260955 A02 01/19/1994 01/24/1994 $0 $7,000 $0 02/04/1994 Y - State Decision  

Investigation Summary

Investigation Nr: 946913
Event: 07/15/1993
FALL - TOWER COLLAPSED DUE TO UNBALANCED LOAD

A power line crew was replacing 0.375-inch-diameter galvanized conductors supported by electric power transmission towers. The towers were originally constructed in 1914, and the power lines were inactive. Two members of the crew were working on a tower that was located in a low lying area and that was known to have its legs under water from time to time. The crew had not inspected the tower before they climbed it, and the tower was not braced or guyed to support the additional stresses that would be imposed. When two of the three conductors supported by the tower were cut, the unbalanced load on the tower caused it to fall over. The two employees fell to the ground with the tower. Both of them were hospitalized for severe injuries sustained in the fall.

Keywords: OVERHEAD POWER LINE, COLLAPSE, POWER LINE WORKER, ELEC UTILITY WORK, FALL, TRANSMISSION TOWER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122136013 Hospitalized injury Fracture Electrical power installers and repairers
2 122136013 Hospitalized injury Fracture Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.