Powered by GoogleTranslate

Inspection Detail

Inspection: 121932701 - Park Drop Forge

Inspection Information - Office: Cleveland Area Office

 

Inspection Nr: 121932701
Report ID: 0522300
Date Opened: 01/30/1996

Site Address:
Park Drop Forge
777 East 79th Street
Cleveland, OH 44103

Mailing Address:
, , 00000

Union Status: Union

SIC:3462

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/12/1996

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 03/27/1996


Related Activity
Type Activity Nr Safety Health
Accident 361848633
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 9 2 11
Current Violations 8 2 10
Initial Penalty $26,500 $0 $0 $1,000 $0 $27,500
Current Penalty $15,630 $0 $0 $648 $0 $16,278
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100147 C06 I 03/26/1996 05/31/1996 $1,625 $2,500 $0 I - Informal Settlement  
2. 01002 Serious 19100147 C07 IIIB 03/26/1996 05/31/1996 $1,625 $2,500 $0 I - Informal Settlement  
3. 01003 Serious 19100303 B01 03/26/1996 04/28/1996 $1,625 $2,500 $0 I - Informal Settlement  
4. 01004 Serious 19100303 H02 II 03/26/1996 04/01/1996 $1,330 $2,000 $0 I - Informal Settlement  
5. 01005A Serious 19100304 E01 I 03/26/1996 04/30/1996 $4,550 $7,000 $0 I - Informal Settlement  
6. 01005B Serious 19100334 B03 03/26/1996 04/30/1996 $0 $0 $0 I - Informal Settlement  
7. 01006 Serious 19100304 E01 IV 03/26/1996 03/29/1996 $2,500 $2,500 $0 I - Informal Settlement Citation has been deleted.
8. 01007 Serious 19100305 J06 I 03/26/1996 04/01/1996 $1,625 $2,500 $0 I - Informal Settlement  
9. 01008A Serious 19100333 C02 03/26/1996 04/28/1996 $1,625 $2,500 $0 I - Informal Settlement  
10. 01008B Serious 19100335 A02 II 03/26/1996 04/28/1996 $0 $0 $0 -  
11. 01009 Serious 19100335 A01 I 03/26/1996 04/28/1996 $1,625 $2,500 $0 I - Informal Settlement  
12. 02001 Other 19040008 03/26/1996 03/29/1996 $648 $1,000 $0 I - Informal Settlement  
13. 02002 Other 19100304 D02 II 03/26/1996 04/13/1996 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 688960
Event: 01/30/1996
BURN - ELECTRICAL FAULT IN DISCONNECT

An employee was replacing 60-ampere fuses in a disconnect box on a 480-volt busway. The disconnect was defective, and the circuit was still energized even when the disconnect's cover was opened. Additionally, the 600-ampere circuit breaker protecting this busway was deliberately blocked; thus, the breaker could not trip when an overload occurred.. As the employee, who did not test the circuit before beginning work, was replacing the fuses, an electrical fault occurred. The employee sustained severe burns as a result of the ensuing electric arc. He was hospitalized for his injuries, but died following surgery 2 days after the accident.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, CIRCUIT BREAKER, ELECTRIC SHOCK, DISCONNECTING MEANS, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 121932701 Fatality Burn/Scald(Heat) Not specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.