Powered by GoogleTranslate

Inspection Detail

Inspection: 121909402 - Columbus Southern Power Company

Inspection Information - Office: Columbus Area Office

 

Inspection Nr: 121909402
Report ID: 0522500
Date Opened: 09/05/1996

Site Address:
Columbus Southern Power Company
State Route 161 And Proprietors Road
Columbus, OH 43085

Mailing Address:
215 North Front Street, Columbus, OH 43215

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/05/1996

Emphasis:

Case Closed: 02/25/1997


Related Activity
Type Activity Nr Safety Health
Accident 100750082
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 A03 10/18/1996 12/20/1996 $5,000 $5,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200750065
Event: 09/04/1996
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU SWITCH

An employee of an electric utility was disconnecting a section of a circuit at a utility pole. He was standing on the ground operating a switch at the bottom of the pole. The section of the switch at the top of the pole became disengaged and fell onto an overhead power line. This energized the switch, and the employee was electrocuted. The circuit had been struck by lightning about a month before the accident, and the ground on the switch had been disconnected because it had burned in two.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, ELECTROCUTED, EQUIPMENT FAILURE, E PTD, EQUIPMENT GROUNDING, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 121909402 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.