Powered by GoogleTranslate

Inspection Detail

Inspection: 120493713 - Eldeco

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 120493713
Report ID: 0454510
Date Opened: 07/15/1993

Site Address:
Eldeco
1530 Bushy Park Rd.
Goose Creek, SC 29445

Mailing Address:
P. O. Box 8197, North Charleston, SC 29418

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/02/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 03/25/1994


Related Activity
Type Activity Nr Safety Health
Accident 360498216
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1
Initial Penalty $2,275 $0 $0 $0 $0 $2,275
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19260403 H 08/16/1993 08/19/1993 $0 $0 $0 08/27/1993 F - Formal Settlement  
2. 01002 Serious 19260416 A03 08/16/1993 08/19/1993 $2,275 $2,275 $0 08/27/1993 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 908624
Event: 07/14/1993
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

AN ELECTRICIAN AND HIS HELPER WERE MAKING CONNECTIONS IN JUNCTION BOX ON A 120-VOLT CIRCUIT ON THE THIRD FLOOR OF A NEW BUILDING. THE BUILDING WAS IN THE FINAL PHASE OF CONSTRUCTION. THE ELECTRICIAN WAS WORKING FROM A WOODEN STEPLADDER. LOCATED IN A CORRIDOR, THE JUNCTION BOX WAS IN A FALSE CEILING, JUST OVER A GROUNDED METAL RACEWAY AND A SUSPENDED CEILING FIXTURE. THE HELPER, WHO WAS WORKING FROM ANOTHER WOODEN STEPLADDER, HAD TO HOLD THE FIXTURE OUT OF THE WAY SO THAT THE ELECTRICIAN COULD REACH THE WORK AREA. THE ELECTRICIAN HAD CHECKED THE DRAWINGS, DETERMINED THAT THE JUNCTION BOX WAS ON CIRCUIT #22, AND HAD OPENED CIRCUIT BREAKER #22. HE THEN LOCKED THE BOX BEFORE MOVING THE CONNECTIONS. IT WAS WARM, AND THE ELECTRICIAN WAS DAMP WITH PERSPIRATION. HE REMOVED AN EXCESS LENGTH OF CONDUCTOR AND THEN STRIPPED AND CONNECTED THE EQUIPMENT GROUNDING CONDUCTOR AND THE GROUNDED CIRCUIT CONDUCTOR. AS HE WAS STRIPPING INSULATION FROM THE (RED) SUPPLY-SIDE UNGROUNDED CIRCUIT CONDUCTOR, HE RECEIVED AN ELECTRIC SHOCK. (HE WAS ABOUT 0.75 INCHES FROM THE LOAD-SIDE UNGROUNDED CIRCUIT CONDUCTOR AT THE TIME.) THE HELPER NOTICED THAT THE ELECTRICIAN WAS IN TROUBLE, BUT COULD NOT SEE WHAT THE PROBLEM WAS. THE HELPER RECEIVED AN ELECTRIC SHOCK WHEN HE TOUCHED THE ELECTRICIAN. THE HELPER FINALLY REMOVED THE ELECTRICIAN FROM CONTACT WITH THE ENERGIZED CONDUCTOR, BUT IT WAS TOO LATE. THE ELECTRICIAN HAD BEEN ELECTROCUTED. AFTER THE ACCIDENT, IT WAS DETERMINED THAT THE LOAD-SIDE UNGROUNDED CIRCUIT CONDUCTOR HAD BEEN CONNECTED TO CIRCUIT #33 AT THE SOURCE AND TO CIRCUIT #22 AT A JUNCTION BOX IN ANOTHER CORRIDOR. THE CIRCUIT BREAKERS AT THE PANELBOARD WERE NUMBERED, BUT NO OTHER EFFORT WAS MADE TO IDENTIFY WHAT THEY CONTROLLED. ADDITIONALLY, NO TESTING WAS PERFORMED TO ENSURE THAT THEY WERE PROPERLY CONNECTED.

Keywords: ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, E C, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120493713 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.