Inspection Detail
Inspection: 120132451 - Ninteman Construction
Inspection Information - Office: San Diego District Office
Site Address:
Ninteman Construction
San Diego State
San Diego, CA 92115
Mailing Address:
4375 Jutland Dr #200, San Diego, CA 92117
Union Status: NonUnion
SIC:1541
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/26/1994
Emphasis:
Case Closed: 12/02/1994
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362249443 |
Investigation Summary
A construction company was building a basement for a new university library. One of the employees on the site lifted a 240-volt concrete drill (Model DM-1186) so that he could hand it to a coworker. He was standing on dry ground at the time. As he placed his hand on a strongback's steel screw to raise the drill to the coworker, he received an electric shock. He was knocked unconscious, but regained consciousness on the way to the hospital. Two other employees had been using the drill the day before and did not experience any problems. The circuit was examined by Bell Electric Company after the accident. It found that there was insufficient continuity in the equipment grounding conductor between a portable outlet box and its source of supply because of dust and dirt accumulation inside the cable connector.
Keywords: UNCONSCIOUSNESS, ELECTRICAL, E C, GROUND FAULT, CORD CONNECTOR, EQUIPMENT GROUNDING, ELECTRIC SHOCK, ELECTRIC DRILL
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 120132451 | Non Hospitalized injury | Electric Shock | Carpenters |