Powered by GoogleTranslate

Inspection Detail

Inspection: 120129309 - Montenay Pacific Power Corp

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 120129309
Report ID: 0950635
Date Opened: 08/12/1994

Site Address:
Montenay Pacific Power Corp
100 Henry Ford Ave
Long Beach, CA 90802

Mailing Address:
P O Box 21549, Long Beach, CA 90801

Union Status: NonUnion

SIC:4953

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/18/1994

Emphasis:

Case Closed: 03/19/1996


Related Activity
Type Activity Nr Safety Health
Accident 362020760
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 3303 11/28/1994 12/15/1994 $5,000 $5,000 $0 01/13/1995 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170358881
Event: 07/27/1994
Employee burned by steam

At 10:38 a.m. on July 27, 1994, Employee #1, of Montenay Pacific Power Corp., a municipal trash incineration facility, was attempting to determine if the ash extractor for boiler #1 had excessive ash buildup. This was normally done by sliding the cover plate on one of the drag conveyors down and looking through the drag conveyor's discharge port into the area above the ash extractor. He had asked that the drag conveyor be bumped so that the conveyor's discharge port could be cleared of any ash overlay. At the same time, the furnace for boiler #1 went positive. When this occurs, air no longer flows from the outside into the furnace. Instead, furnace gases and ash flow through any available opening out into the surrounding environment. Employee #1 was scalded or burned when steam and debris spewed from openings in the ram and south drag conveyor. He was transported to St. Mary Medical Center in Long Beach and was then transferred to the burn ward at Torrance Memorial Medical Center. He suffered second-degree burns to 30 to 35 percent of his body including his hands, arms, face, back, neck, and bilateral extremities. Employee #1 had been wearing heavy cotton long sleeve overalls, a hard hat, safety glasses with side shields, and leather gloves. The exact cause for this particular excursion into the positive pressure range is unknown. It is not unusual, although no one interviewed recalled an excursion of this apparent magnitude. The board operator reports, based on no recording of the event on the distributive control system, that the excursion lasted less than 60 seconds. Past excursions have been attributed to trash having rapid burning capacity, such as a partially filled propane bottle exploding, or trash which can release large volumes of inert gas or steam, such as an explosion of a partially filled water heater. Either event simply pushes the furnace gases and debris out of the furnace. The port holes upstairs in the furnace grate area have deflecting plates between the viewer and the furnace, but no such arrangement exists on the ground floor for ash extractor area.

Keywords: BURN, FURNACE, WORK RULES, BOILER, STEAM, HIGH PRESSURE, ARM, FACE, ACCIDENTAL DISCHARGE, UNGUARDED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120129309 Hospitalized injury Burn/Scald(Heat) Precious stones and metals workers (jewelers)
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close