Powered by GoogleTranslate

Inspection Detail

Inspection: 120023080 - Thunder Electrical

Inspection Information - Office: San Francisco District Office

 

Inspection Nr: 120023080
Report ID: 0950611
Date Opened: 06/08/1995

Site Address:
Thunder Electrical
150 Spear St.
San Francisco, CA 94105

Mailing Address:
, , 00000

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/08/1995

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/23/1995


Related Activity
Type Activity Nr Safety Health
Accident 362188427
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $3,500 $0 $0 $0 $0 $3,500
Current Penalty $0 $0 $0 $110 $0 $110
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A03 08/11/1995 08/16/1995 $110 $3,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 170204655
Event: 06/05/1995
BURN - ELECTRICAL FAULT IN MOTOR STARTER

An electrician was troubleshooting a problem in a motor control center in a high rise building. A heating, ventilation, and air conditioning condenser water pump had tripped a circuit breaker. The employee apparently determined that the 480-volt terminal block containing the starter for the pump had shorted conductors and repaired it. As the employee tightened the lugs on the front of the terminal block in the process of reinstalling it, an electrical fault occurred. The ensuing electric arc burned him and knocked him backwards, unconscious, to the floor. It was believed that the cause of the fault was either that prongs at the rear of the block were not properly aligned and touched each other when tightened or that something behind fell onto the prongs.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL FAULT, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120023080 Non Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close