Inspection Detail
Inspection: 119974285 - Ca Corrections
Inspection Information - Office: Fresno District Office
Site Address:
Ca Corrections
1 Kings Way
Avenal, CA 93204
Mailing Address:
P O Box 8, Avenal, CA 93204
Union Status: Union
SIC:9223
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 08/21/1997
Emphasis:
Case Closed: 01/15/1999
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362049892 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | 2 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 08/29/1997 | 05/15/1997 | $0 | $0 | $0 | - | ||
| 2. | 02001 | Serious | 23200002 A | 08/29/1997 | 09/22/1997 | $0 | $0 | $0 | 10/01/1997 | J - ALJ Decision |
Investigation Summary
An electrician was installing a Prescolite EFP5 emergency lighting ballast in an automobile tool room in a vocational education building at a prison. He had pulled the ungrounded circuit conductor from a T-type conduit body located 4.4 meters above the floor. He was standing on the seventh step of a 3-meter-tall fiberglass and aluminum ladder. To gain access to the conductor, which was to be connected to the ballast, the employee had climbed between a lighting fixture that was 3 meters above the floor and a 102-millimeter-diameter metal pipe that was 3.7 meters above the floor. He was also working around a metal sprinkler pipe. The employee, who was not wearing rubber insulating gloves, contacted the 277-volt conductor, received an electric shock, and fell to the floor. He was electrocuted.
Keywords: BALLAST--LIGHTING, ELEC PROTECT EQUIP, LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119974285 | Fatality | Electric Shock | Electricians |
Translate