Powered by GoogleTranslate

Inspection Detail

Inspection: 119946341 - Frito-Lay, Inc.

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 119946341
Report ID: 0950633
Date Opened: 04/27/1994

Site Address:
Frito-Lay, Inc.
9535 Archibald Avenue
Rancho Cucamonga, CA 91730

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2041

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/27/1994

Emphasis:

Case Closed: 12/20/1994


Related Activity
Type Activity Nr Safety Health
Accident 362241275
Complaint 76214923 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 23200002 A03 10/13/1994 10/19/1994 $5,000 $5,000 $0 -  

Investigation Summary

Investigation Nr: 170356059
Event: 04/14/1994
BURN - ELECTRICAL FAULT IN SWITCHBOARD

An employee of a snack food manufacturing company was assisting employees of a contractor performing infrared inspection of switchboards, panelboards, and electrical cabinets. The snack food employee, who was not wearing electrical protective equipment, had opened the left side of the roll-up door on a switchboard (identified as SWBD-DSA). With a flathead screwdriver in his left hand, he then loosened a screw on the right side of the switchboard one quarter turn. While he was holding the door open with his right hand and using the screwdriver in his left hand, an electrical fault occurred in the switchboard. (It was theorized that the fault occurred as a result of the screwdriver slipping into contact with the circuit breaker buses.) The employee sustained serious burns to his right hand and flash burns to his face and eyes as a result of the ensuing electric arc. He was hospitalized for his injuries.

Keywords: BURN, E GI II, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, INSULATED TOOL, SWITCHBOARD, BUSBAR, ELECTRICAL WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119946341 Hospitalized injury Burn/Scald(Heat) Not specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close