Powered by GoogleTranslate

Inspection Detail

Inspection: 119861383 - Spartech Plastic

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 119861383
Report ID: 0950642
Date Opened: 10/18/1993

Site Address:
Spartech Plastic
14263 Gannet St
La Mirada, CA 90638

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3081

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/27/1994

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/25/2008


Related Activity
Type Activity Nr Safety Health
Accident 362161077
Accident 362164428
Complaint 76251263 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $10,000 $0 $0 $400 $0 $10,400
Current Penalty $5,400 $0 $0 $400 $0 $5,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 01/27/1994 01/27/1994 $400 $400 $0 02/25/1994 J - ALJ Decision  
2. 02001 Serious 23200002 A 01/27/1994 01/27/1994 $5,000 $5,000 $0 02/25/1994 J - ALJ Decision  
3. 03001 Serious 3203 A 6 01/27/1994 01/27/1994 $400 $5,000 $0 02/25/1994 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170606123
Event: 10/16/1993
BURN - ELECTRICAL FAULT IN PANELBOARD

Three maintenance workers were replacing a circuit breaker on a 480-volt, 800-ampere circuit. The job had been scheduled for a Sunday, with all equipment shut down. However, no one called the electric utility to deenergize the service drop from the utility pole. The crew was aware that the circuit was still energized, but decided to perform the job anyway. The two employees who were performing the work were standing on a wooden pallet for insulation from ground. Neither of them was wearing rubber insulating gloves or eye protection. They disconnected the load-side conductors and pulled the circuit breaker out of the panelboard while it was still attached to the energized supply-side conductors. As they were removing the screws for the supply-side conductors, they caused an electrical fault. The ensuing electric arc seriously burned all three employees, killing one of them and hospitalizing the other two.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119861383 Hospitalized injury Burn/Scald(Heat) Industrial machinery repairers
2 119861383 Hospitalized injury Burn/Scald(Heat) Industrial machinery repairers
3 119861383 Fatality Burn/Scald(Heat) Industrial machinery repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close