Powered by GoogleTranslate

Inspection Detail

Inspection: 119783694 - Union Cold Storage

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 119783694
Report ID: 0950642
Date Opened: 10/28/1996

Site Address:
Union Cold Storage
1525 Industrial Street
Los Angeles, CA 90021

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:4222

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Health

Close Conference: 12/30/1996

Planning Guide: Health-Manufacturing

Emphasis:

Case Closed: 03/13/1999


Related Activity
Type Activity Nr Safety Health
Accident 362533267
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 3 4
Current Violations 4 4
Initial Penalty $2,500 $0 $0 $435 $0 $2,935
Current Penalty $0 $0 $0 $685 $0 $685
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A 12/23/1996 01/25/1997 $0 $125 $0 02/10/1997 J - ALJ Decision  
2. 01002 Other 6151 C04 12/23/1996 01/08/1997 $125 $125 $0 02/10/1997 W - Empr Withdrew  
3. 01003 Other 4650 E 12/23/1996 01/06/1997 $185 $185 $0 -  
4. 02001 Other 3329 D 12/23/1996 01/25/1997 $375 $2,500 $0 02/10/1997 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170633390
Event: 10/28/1996
Employee burned by release of pressurized ammonia

Employee #1, of Union Central Cold Storage, Inc., Los Angeles, CA, was helping to remove a valve housing assembly. When the housing parts were separated, a portion of the line fell and released pressurized ammonia. Employee #1 sustained third-degree burns on his hands, legs, and abdomen. Subsequent investigation revealed that the employer had purged the pressurized ammonia from the lines, and the gauges attached to them read zero. However, a 6 ft section of line had not been depressurized, and the rear pressure check valve was in the 'up' position when it was supposed to be down. Employee #1 also stated that the bolts holding the valve assembly should have been slightly loosened, but they had been completely removed.

Keywords: ABDOMEN, AMMONIA, UNSECURED, WORK RULES, GAS, HIGH PRESSURE, VALVE, CHEMICAL BURN, HAND, LEG

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119783694 Hospitalized injury Burn(Chemical) Miscellaneous plant and system operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.