Inspection: 119781763 - Shell Oil Products Us

Inspection Information - Office: Labor Enforcement Task Force (Letf) Unit - Central

 

Inspection Nr: 119781763
Report ID: 0950664
Date Opened: 02/08/2007

Site Address:
Shell Oil Products Us
2101 Pacific Coast Hwy
Wilmington, CA 90744

Mailing Address:
, , 00000

Union Status: Union

SIC:2911

NAICS: 324110/Petroleum Refineries


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/31/2007

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/18/2008


Related Activity
Type Activity Nr Safety Health
Accident 362413460
Accident 362413973
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 1 5
Current Violations
Initial Penalty $48,150 $0 $0 $675 $0 $48,825
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 29400006 J 07/31/2007 09/04/2007 $0 $675 $0 F - Formal Settlement Citation has been deleted.
2. 02001 Other 3203 A04 07/31/2007 08/14/2007 $0 $18,000 $0 F - Formal Settlement Citation has been deleted.
3. 03001 Serious 3203 A07 07/31/2007 08/14/2007 $0 $6,075 $0 F - Formal Settlement Citation has been deleted.
4. 04001 Serious 3328 G 07/31/2007 08/14/2007 $0 $18,000 $0 F - Formal Settlement Citation has been deleted.
5. 05001 Serious 5189 J02 C 07/31/2007 08/14/2007 $0 $6,075 $0 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 201039013
Event: 02/08/2007
Employee Is Burned in Electrical Arc Flash

At approximately 2:18 p.m. on February 8, 2007, coworker #5 bump started motor M-3665 by pushing the start switch at motor M-3665 and went to observe the rotation of P-1386's shaft. As he approached P-1386's shaft, he noted that the shaft was running in the right direction, but not at the proper speed. He decided to shut motor M-3665 down and radioed Employee #1, located at the Motor Control Center-MCC -35A, CRU 3 south switch gear pad, with coworkers #2, #3 and #4, and asked him to check if motor M-3665 had tripped. Employee #1 went to Motor M-3665's Mulitin Motor relay, located immediately to the left of the Motor M-3665's motor starter's electrical cabinet cubicle, and checked if there was any indication that Motor M-3665 had tripped. At approximately 2:19 PM as Employee #1 arrived at the Motor M-3665 multilin motor relay, a humming and hissing sound came from motor M-3665's motor starter cubicle. This was followed by an orange fireball, opening the motor M-3665's motor starter's cubicle hinged door and striking Employee #1. He was struck in the front of the body and driven into the distribution volt center positioned behind him. Employee #1 and coworkers #1, #2,#3, and #4 were taken to a hospital, where they were treated for burns to the hands, face, back of neck and torso. Employee #1 burns were to such a degree that he was transferred to a burn center and was hospitalized.

Keywords: BURN, ELECTRIC ARC, ABDOMEN, FIRE, THIGH, ARM, FACE, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119781763 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.