Powered by GoogleTranslate

Inspection Detail

Inspection: 119668085 - Express Electric (Brandon Const Gc)

Inspection Information - Office: Oakland District Office

 

Inspection Nr: 119668085
Report ID: 0950614
Date Opened: 10/12/1995

Site Address:
Express Electric (Brandon Const Gc)
6379 Clark Ave
Dublin, CA 94568

Mailing Address:
1071 San Pablo Ave., Albany, CA 94706

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/01/1996

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/05/1997


Related Activity
Type Activity Nr Safety Health
Accident 361621105
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 3 1 4
Initial Penalty $3,870 $0 $0 $85 $0 $3,955
Current Penalty $910 $0 $0 $85 $0 $995
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 B 02/27/1996 03/12/1996 $85 $85 $0 04/22/1996 J - ALJ Decision  
2. 02001 Serious 1509 A 02/27/1996 03/12/1996 $435 $3,000 $0 04/22/1996 J - ALJ Decision  
3. 03001 Serious 23200002 A03 02/27/1996 03/12/1996 $435 $435 $0 04/22/1996 J - ALJ Decision  
4. 04001 Serious 23200002 A04 02/27/1996 03/12/1996 $40 $435 $0 04/22/1996 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170722474
Event: 10/01/1995
BURN - ELECTRICAL FAULT IN SWITCHGEAR

Two electricians were burned in separate accidents while working in an ITE main switchgear. (Employee #1 was burned on October 1, 1995. Employee #2 was burned on October 2, 1995.) Each was removing 100-ampere and 50-ampere circuit breakers at the time of his accident. Based on investigation of burned hardware in the switchgear cabinet and in the circuit breakers, investigators concluded that a loose connection in the hardware and the elevator circuit breaker screws caused phase-to-phase electrical faults. The ensuing electric arcs burned the employees and caused fires. The 480-volt switchgear was worked energized though the loads were disconnected. The employees were working without rubber insulating gloves and safety glasses. They were each hospitalized with serious burns on their faces, arms, and hands.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, CIRCUIT BREAKER, ELECTRICAL FAULT, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119668085 Hospitalized injury Burn/Scald(Heat) Electricians
2 119668085 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.