Powered by GoogleTranslate

Inspection Detail

Inspection: 116526419 - C. Damron Jr. Electric, Incorporated

Inspection Information - Office: Charleston Area Office

 

Inspection Nr: 116526419
Report ID: 0316400
Date Opened: 01/08/1998

Site Address:
C. Damron Jr. Electric, Incorporated
408 Chestnut Street
South Charleston, WV 25309

Mailing Address:
Post Office Box 9186, South Charleston, WV 25309

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/16/1998

Emphasis:

Case Closed: 08/01/2005


Related Activity
Type Activity Nr Safety Health
Accident 361891807
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $3,000 $0 $0 $300 $0 $3,300
Current Penalty $3,000 $0 $0 $300 $0 $3,300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 04/15/1998 04/27/1998 $1,500 $1,500 $0 -  
2. 01002 Serious 19260095 A 04/15/1998 04/27/1998 $1,500 $1,500 $0 -  
3. 02001 Other 19040008 A 04/15/1998 04/27/1998 $300 $300 $0 -  

Investigation Summary

Investigation Nr: 170748610
Event: 11/26/1997
BURN - ELECTRICAL FAULT IN SWITCHBOARD

Two employees of an electrical contractor were removing a 225-ampere circuit breaker from a 1600-ampere, 277/480-volt, Square D switchboard. The employees had not deenergized the switchboard before starting the job, nor were they wearing personal protective equipment. Employee #1 was performing the task, kneeling in front of the switchboard. Employee #2 was kneeling to his left. An electrical fault occurred, and the ensuing electric arc burned the two employees and ignited their clothing. Employee #l received burns to his chest, face, and arms. He died from his injuries. Employee #2 received burns to his right side, and he burned his hands from putting out the fire on himself and his coworker.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI IV, ELECTRICAL, SWITCHBOARD, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 116526419 Fatality Burn/Scald(Heat) Electricians
2 116526419 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.