Powered by GoogleTranslate

Inspection Detail

Inspection: 115470775 - Mason County Pud #3

Inspection Information - Office: Dosh Tumwater Service Location, Tumwater, Wa

 

Inspection Nr: 115470775
Report ID: 1055340
Date Opened: 04/18/1994

Site Address:
Mason County Pud #3
116 East K St
Shelton, WA 98584

Mailing Address:
Po Box 2148, Shelton, WA 98584

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 06/27/1994

Emphasis:

Case Closed: 02/27/1995


Related Activity
Type Activity Nr Safety Health
Accident 361194517
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 1 1
Initial Penalty $28,000 $0 $0 $0 $0 $28,000
Current Penalty $5,600 $0 $0 $0 $0 $5,600
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 0456501103 08/12/1994 06/27/1994 $5,600 $5,600 $0 08/31/1994 L - State Settlement Citation has been deleted.
2. 01002 Serious 0456502707 08/12/1994 06/27/1994 $5,600 $5,600 $0 08/31/1994 L - State Settlement Citation has been deleted.
3. 01003 Serious 0456502712 08/12/1994 06/27/1994 $5,600 $5,600 $0 08/31/1994 L - State Settlement Citation has been deleted.
4. 01004 Serious 0456503506 B 01 08/12/1994 06/27/1994 $5,600 $5,600 $0 08/31/1994 L - State Settlement Citation has been deleted.
5. 01005A Serious 0456501103 11/03/1994 06/27/1994 $5,600 $5,600 $0 L - State Settlement  
6. 01005B Serious 0456503506 B 01 11/03/1994 06/27/1994 $0 $0 $0 L - State Settlement  
7. 01005C Serious 0456502602 A 11/03/1994 06/27/1994 $0 $0 $0 L - State Settlement  

Investigation Summary

Investigation Nr: 170097000
Event: 04/15/1994
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A power line crew was dispatched to a substation to perform maintenance work on switchgear. Their supervisor gave switching orders to the crew over a radio, and they apparently carried them out. The crew then waited for another electric utility owning power lines running into the station to perform their switching. After gaining clearance but without testing or grounding the circuits, the crew began their work. As one of the power line workers on the crew was cleaning a switchgear contact, his arm contacted an energized 7200-volt switch. He received an electric shock and sustained severe burns. The employee was hospitalized, and his right arm was amputated below the elbow as a result of his injuries.

Keywords: BURN, AMPUTATED, ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, ARM

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 115470775 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.