Inspection Detail
Inspection: 114988918 - Olin Brass Corp
Inspection Information - Office: Indiana Department Of Labor
Site Address:
Olin Brass Corp
1800 S Holt Rd
Indianapolis, IN 46241
Mailing Address:
, , 00000
Union Status: Union
SIC:3351
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/01/1993
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 02/02/1994
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361311129 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 5 | 2 | 7 | |||
| Current Violations | 4 | 3 | 7 | |||
| Initial Penalty | $22,000 | $0 | $0 | $0 | $0 | $22,000 |
| Current Penalty | $12,625 | $0 | $0 | $0 | $0 | $12,625 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100303 B01 | 12/22/1993 | 01/09/1994 | $3,750 | $5,000 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100303 H03 | 12/22/1993 | 01/09/1994 | $2,625 | $3,500 | $0 | I - Informal Settlement | ||
| 3. | 01003A | Serious | 19100333 A01 | 12/22/1993 | 01/09/1994 | $3,750 | $5,000 | $0 | I - Informal Settlement | ||
| 4. | 01003B | Serious | 19100333 B02 IIIA | 12/22/1993 | 01/09/1994 | $0 | $0 | $0 | I - Informal Settlement | ||
| 5. | 01004 | Serious | 19100335 A01 I | 12/22/1993 | 01/09/1994 | $2,500 | $5,000 | $0 | I - Informal Settlement | ||
| 6. | 01005 | Other | 19100335 A01 II | 12/22/1993 | 01/09/1994 | $0 | $3,500 | $0 | I - Informal Settlement | ||
| 7. | 02001 | Other | 19100147 C04 I | 12/22/1993 | 01/09/1994 | $0 | $0 | $0 | - | ||
| 8. | 02002 | Other | 19100332 B01 | 12/22/1993 | 01/09/1994 | $0 | $0 | $0 | - |
Investigation Summary
AN ELECTRICIAN WAS REPLACING A 6900-VOLT AC CONTACTOR FOR AN INDUCTION HEATER ON A BAR MILL. THE CABINET ON WHICH THE EMPLOYEE WAS WORKING WAS LOCATED ON A METAL PLATFORM THAT WAS ATTACHED TO THE FRAME OF THE BUILDING. THE BUILDING'S STRUCTURE WAS USED AS A GROUNDING ELECTRODE; THUS, THE PLATFORM WAS AT GROUND POTENTIAL. THE 6900-VOLT POWER SUPPLY TO THE CABINET HAD NOT BEEN DEENERGIZED BEFORE THE EMPLOYEE BEGAN HIS WORK. AFTER THE NEW CONTACTOR HAD BEEN SLID INTO PLACE AND LOCKED DOWN, THE ELECTRICIAN REACHED INTO THE LEFT SIDE OF THE CABINET TO RETRIEVE A 120-VOLT CONTROL VOLTAGE PLUG TO COMPLETE THE INSTALLATION. AS HE DID SO, HE CONTACTED AN ENERGIZED SURGE COIL. HE RECEIVED AN ELECTRIC SHOCK AND WAS TRANSPORTED TO A HOSPITAL. HE DIED OF ELECTROCUTION AT 3:10 PM THAT SAME DAY.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL CABINET
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 114988918 | Fatality | Electric Shock | Misc. electrical & electronic equipment repairers |