Inspection: 112176896 - Cal State Northridge

Inspection Information - Office: Van Nuys District Office

 

Inspection Nr: 112176896
Report ID: 0950643
Date Opened: 04/24/1997

Site Address:
Cal State Northridge
18111 Nordhoff Street
Northridge, CA 91330

Mailing Address:
, , 00000

Union Status: Union

SIC:8221

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: StateGovt

Safety/Health: Safety

Close Conference: 06/18/1997

Emphasis:

Case Closed: 07/27/1997


Related Activity
Type Activity Nr Safety Health
Accident 362289720
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 3 5
Current Violations 2 3 5
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A07 C 07/09/1997 08/11/1997 $0 $0 $0 -  
2. 01002 Other 23900041 A 07/09/1997 08/11/1997 $0 $0 $0 -  
3. 01003 Other 25300086 A 07/09/1997 08/11/1997 $0 $0 $0 -  
4. 02001 Serious 23200002 A 1 07/09/1997 07/25/1997 $0 $0 $0 -  
5. 03001 Serious 23200002 A 3 07/09/1997 08/11/1997 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 201110442
Event: 04/03/1997
BURN - ELECTRICAL FAULT IN PANELBOARD

An experienced electrician was working in the motor control center for the art design center at a university. He was working as the emergency call electrician, which was not his regular job. The electrician was sent to repair a problem with the exhaust fans at the center. He found that the circuit breaker for the exhaust fans was open and could not be reset. He began to remove the circuit breaker from the panelboard without deenergizing the panelboard. (It was common practice at the university to work on a circuit breaker without deenergizing the circuit.) As he was loosening the bolts holding the breaker, his nut driver contacted an energized part, creating an electrical fault. The ensuing electric arc burned the employee's face, scalp, and neck. The injured employee was taken to a hospital for emergency treatment and then transferred to a burn center, where he was hospitalized for his injuries.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, HAND TOOL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 112176896 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.