Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 112016860 - Aman Environmental Construction, Inc.

Inspection Information - Office: Ca Fresno

Nr: 112016860Report ID: 0950625Open Date: 10/08/1996

Aman Environmental Construction, Inc.
Edwards Afb
Rosamond, CA 93560
Union Status: NonUnion
SIC: 1795/Wrecking and Demolition Work
Mailing: 614 E. Edna Place, Covina, CA 91723

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:10/08/1996
Close Case:12/08/1997

Related Activity:TypeIDSafetyHealth
 Accident361373715    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $6,875 $0 $0 $0 $0 $6,875
Current Penalty $0 $0 $0 $0 $0 $0
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
Deleted 1. 01001 Serious 23200004 A02 10/17/1996 10/25/1996 $0 $5,000 $0 11/24/1996 J - ALJ Decision
  2. 02001 Serious 23400023 10/17/1996 12/11/1996 $0 $1,875 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 170623482Event: 04/17/1996Burn - Electrical Fault In Electrical Box
Two employees were removing a conduit above a 480-volt electrical box. The employees were cutting the metal conduit with a saw. The metal filings from their cutting fell onto energized terminals inside the box, causing an electrical fault. The ensuing electric arc severely burned one of the employees on both hands. He was hospitalized for his injuries.
Keywords: burn, electric arc, e gi iv, electrical, conduit, electrician, electrical work, lockout, electrical box, electrical fault
Inspection Degree Nature Occupation
1 112016860 Hospitalized injury Burn/Scald(Heat) Construction trades, n.e.c.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.