Inspection: 112004866 - San Diego Gas & Electric

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 112004866
Report ID: 0950632
Date Opened: 03/31/1992

Site Address:
San Diego Gas & Electric
4500 Otay Mesa Rd
San Diego, CA 92173

Mailing Address:
114 10th Ave, San Diego, CA 92101

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/28/1992

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/11/1992


Related Activity
Type Activity Nr Safety Health
Accident 361366842
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $1,050 $0 $0 $2,000 $0 $3,050
Current Penalty $1,050 $0 $0 $2,000 $0 $3,050
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2944 G 09/03/1992 09/03/1992 $700 $700 $0 -  
2. 02001 Serious 2944 H02 E 09/03/1992 09/03/1992 $350 $350 $0 -  
3. 03001 Other 2944 H01 C 08/28/1992 08/28/1992 $2,000 $2,000 $0 -  

Investigation Summary

Investigation Nr: 170190466
Event: 03/11/1992
ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS THRU HAND TOOL

A crew of electricians for an electric utility was performing routine maintenance in a substation. A journeyman electrician and an apprentice were assigned to service 12-kilovolt bus disconnects. The disconnects were not originally scheduled in this job; however, since they were available for servicing, the foreman decided to do them as well. One end of the line (#102) to the disconnects had already been deenergized, locked out, and tagged. the electrician was instructed to deenergize the other end of the line (#101). The electrician was then supposed to service the deenergized contacts at both ends before reenergizing disconnect #101. However, the electrician reenergized disconnect #101 before he serviced disconnect #102. He received an electric shock when his oil squirt can contacted the energized conductor at disconnect #102. He was hospitalized for his injuries.

Keywords: ELECTRICAL, ELECTRIC SWITCH, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, E PTD, SUBSTATION, ELECTRIC SHOCK, HAND TOOL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 112004866 Hospitalized injury Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.