Powered by GoogleTranslate

Inspection Detail

Inspection: 111253803 - Seattle City Light

Inspection Information - Office: Dosh Spokane Service Location, Spokane, Wa

 

Inspection Nr: 111253803
Report ID: 1055360
Date Opened: 03/13/1992

Site Address:
Seattle City Light
Martin Luther King Way & South Alaska
Seattle, WA 98104

Mailing Address:
1015 Third Ave, Seattle, WA 98104

Union Status: Union

SIC:9131

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 03/13/1992

Emphasis: L:Euc

Case Closed: 07/09/1992


Related Activity
Type Activity Nr Safety Health
Accident 361193279
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $320 $0 $0 $0 $0 $320
Current Penalty $320 $0 $0 $0 $0 $320
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 0456502903 05/08/1992 03/13/1992 $320 $320 $0 -  

Investigation Summary

Investigation Nr: 170000509
Event: 03/11/1992
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU UTIL. POLE

A power line crew was setting a 16.8-meter dry cedar utility pole. They were lifting the pole between the center phase and one of the outside phase conductors of an overhead power line. The crew had installed an insulating barrier on the top of the pole and were using a pole-setting derrick truck to position the pole. Two employees were controlling the butt of the pole using two polyvinyl chloride pole risers. The pole risers were not large enough to properly grip the pole. The pole slipped in one of the risers, allowing the pole to contact the power line below the insulating barrier. The employee whose riser slipped apparently received an electric shock (he said he felt something when the pole contacted the power line). He was hospitalized for his injury.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 111253803 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close