Powered by GoogleTranslate

Inspection Detail

Inspection: 110691581 - Midland Water Purification

Inspection Information - Office: Miosha General Industry Safety & Health Division

 

Inspection Nr: 110691581
Report ID: 0552652
Date Opened: 06/28/1991

Site Address:
Midland Water Purification
2607 Bay City Rd
Midland, MI 48640

Mailing Address:
333 W Ellsworth, Po Box 1647, Midland, MI 48640

Union Status: Union

SIC:4941

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/28/1991

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/27/1991


Related Activity
Type Activity Nr Safety Health
Accident 361004500
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $840 $0 $0 $0 $0 $840
Current Penalty $840 $0 $0 $0 $0 $840
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 40810011 A 07/22/1991 07/25/1991 $0 $0 $0 -  
2. 01002 Serious 40810011 C 07/22/1991 07/25/1991 $420 $420 $0 -  
3. 01003 Serious 4081338708 07/22/1991 07/25/1991 $420 $420 $0 -  

Investigation Summary

Investigation Nr: 170228308
Event: 06/27/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYEE WAS REMOVING A BREAKDOWN TRANSFORMER FROM INSIDE A CABINET THAT ALSO HOUSED A KNIFE SWITCH. THE UPPER SECTION OF THE 4160-VOLT KNIFE SWITCH WAS ENERGIZED. THE EMPLOYEE POSITIONED HIMSELF INSIDE THE CABINET SO THAT HE WAS EXPOSED TO CONTACT WITH THE SWITCH. IN REMOVING THE BOLTS FOR THE TRANSFORMER, THE EMPLOYEE CONTACTED ENERGIZED PARTS OF THE SWITCH WITH HIS ELBOW. HE WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRICAL CABINET

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 110691581 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.