Powered by GoogleTranslate

Inspection Detail

Inspection: 110324878 - Sunrise Industry America, Inc.

Inspection Information - Office: El Paso Area Office

 

Inspection Nr: 110324878
Report ID: 0627410
Date Opened: 10/13/1995

Site Address:
Sunrise Industry America, Inc.
9600 Plaza Circle
El Paso, TX 79927

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3462

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/13/1995

Emphasis:

Case Closed: 11/22/1995


Related Activity
Type Activity Nr Safety Health
Accident 360341135
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 1 5
Current Violations 4 1 5
Initial Penalty $8,825 $0 $0 $0 $0 $8,825
Current Penalty $5,500 $0 $0 $0 $0 $5,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100095 C01 10/30/1995 12/18/1995 $400 $825 $0 I - Informal Settlement  
2. 01002A Serious 19100106 E06 II 10/30/1995 11/02/1995 $800 $1,575 $0 I - Informal Settlement  
3. 01002B Serious 19100106 E02 III 10/30/1995 11/02/1995 $0 $0 $0 I - Informal Settlement  
4. 01003 Serious 19100132 D01 10/30/1995 12/04/1995 $300 $825 $0 I - Informal Settlement  
5. 01004A Serious 19100332 B01 10/30/1995 12/18/1995 $4,000 $5,600 $0 I - Informal Settlement  
6. 01004B Serious 19100333 A02 10/30/1995 12/18/1995 $0 $0 $0 I - Informal Settlement  
7. 01004C Serious 19100333 B02 I 10/30/1995 12/18/1995 $0 $0 $0 I - Informal Settlement  
8. 01004D Serious 19100333 C02 10/30/1995 12/18/1995 $0 $0 $0 I - Informal Settlement  
9. 01004E Serious 19100335 A01 I 10/31/1995 11/03/1995 $0 $0 $0 I - Informal Settlement  
10. 01004F Serious 19100335 A02 IA 10/30/1995 12/18/1995 $0 $0 $0 I - Informal Settlement  
11. 02001 Other 19100151 C 10/30/1995 12/18/1995 $0 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14446017
Event: 10/12/1995
BURN - ELECTRICAL FAULT IN PANELBOARD

Three employees were replacing a fuse in a 480-volt, 100-ampere Spectra Series General Electric panelboard. None of the employees had been trained for this procedure nor were they wearing personal protective equipment of any kind. The fuse box was about 1.5 meters above the floor. During the operation, the fuse failed, and one of the metal ends of the fuse became lodged between the terminals two of the in-coming conductors. This caused an electrical fault. The ensuing electric arc burned the three employees, who were standing about 1 meter from the panelboard. Employee #1 sustained third degree burns from his waist up and was placed on life support. The other two employees sustained third degree burns on their faces, shoulders, and chests. All three employees were hospitalized for their injuries.

Keywords: BURN, CLOTHING, FUSE, ELECTRIC ARC, E GI III, ELECTRICAL, PANELBOARD, EQUIPMENT FAILURE, ELECTRICAL FAULT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 110324878 Hospitalized injury Burn/Scald(Heat) Managers and administrators, n.e.c
2 110324878 Hospitalized injury Burn/Scald(Heat) Supervisors, production occupations
3 110324878 Hospitalized injury Burn/Scald(Heat) Supervisors, production occupations
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.