Powered by GoogleTranslate

Inspection Detail

Inspection: 110293180 - Vaughn Electric Co.

Inspection Information - Office: Toledo Area Office

 

Inspection Nr: 110293180
Report ID: 0524700
Date Opened: 01/17/1990

Site Address:
Vaughn Electric Co.
St. Rt. 362 3900 Canal Rd. #1
Minster, OH 45865

Mailing Address:
P.O. Box 96, Carey, OH 43316

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/28/1990

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/10/1992


Related Activity
Type Activity Nr Safety Health
Accident 360714745
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 9 1 4 14
Current Violations 3 3 6
Initial Penalty $7,100 $7,000 $0 $700 $0 $14,800
Current Penalty $1,700 $0 $0 $100 $0 $1,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 05/29/1990 06/06/1990 $800 $800 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19260050 E 05/29/1990 01/01/1991 $100 $800 $0 06/19/1990 F - Formal Settlement  
3. 01003 Serious 19260050 F 05/29/1990 06/01/1990 $800 $800 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
4. 01004 Serious 19260059 E01 05/29/1990 06/21/1990 $800 $800 $0 06/19/1990 F - Formal Settlement  
5. 01005 Serious 19260059 G01 05/29/1990 06/01/1990 $800 $800 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
6. 01006 Serious 19260059 G08 05/29/1990 06/01/1990 $800 $800 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
7. 01007 Serious 19260059 H 05/29/1990 07/02/1990 $800 $800 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
8. 01008 Serious 19260951 B01 05/29/1990 06/01/1990 $800 $800 $0 06/19/1990 F - Formal Settlement  
9. 01009 Other 19260950 E01 II 05/29/1990 07/02/1990 $0 $700 $0 06/19/1990 F - Formal Settlement  
10. 02001 Willful 19260950 C01 05/29/1990 06/01/1990 $7,000 $7,000 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
11. 03001 Other 19030002 A01 05/29/1990 06/01/1990 $50 $100 $0 06/19/1990 F - Formal Settlement  
12. 03002 Other 19040002 A 05/29/1990 06/25/1990 $50 $100 $0 06/19/1990 F - Formal Settlement  
13. 03003 Other 19040004 05/29/1990 07/31/1990 $100 $100 $0 06/19/1990 F - Formal Settlement Citation has been deleted.
14. 03004 Other 19040008 05/29/1990 06/01/1990 $400 $400 $0 06/19/1990 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14515035
Event: 01/12/1990
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

AN EMPLOYEE WAS INSTALLING A TRANSFORMER ON A NEW 40-FOOT, CLASS 3 UTILITY POLE. THE 7200-VOLT PRIMARY OVERHEAD POWER LINE ON THE POLE WAS ENERGIZED. THE TRANSFORMER WAS LOCATED ABOUT 8 INCHES BELOW AN EYEBOLT THAT SUPPORTS THE POWER LINE CONDUCTOR. THE EMPLOYEE WAS WORKING FROM A TWO-PERSON BUCKET OF AN ALTEC AERIAL LIFT WITH A 50-FOOT REACH. ALTHOUGH INSULATING EQUIPMENT WAS AVAILABLE, THE POWER LINE WAS NOT COVERED WITH INSULATING EQUIPMENT, NOR WAS THE EMPLOYEE WEARING RUBBER INSULATING GLOVES OR SLEEVES. THE EMPLOYEE WAS EITHER INSTALLING A JIB ON THE POLE OR ADJUSTING IT, WHEN HE CONTACTED THE OVERHEAD LINE WITH HIS LEFT SHOULDER. FROM THE BURN MARKS ON THE EQUIPMENT, IT APPEARED THAT THE EMPLOYEE HAD ONE OR BOTH HANDS ON THE JIB WHEN HE CONTACTED THE POWER LINE AT A POINT NEAR THE DEAD-END CLAMP. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 110293180 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.