Powered by GoogleTranslate

Inspection Detail

Inspection: 110089380 - Electric Services, Inc.

Inspection Information - Office: Jacksonville Area Office

 

Inspection Nr: 110089380
Report ID: 0419700
Date Opened: 07/19/1995

Site Address:
Electric Services, Inc.
945 N. Temple Avenue
Starke, FL 32091

Mailing Address:
306 South 6th Street, Leesburg, FL 34748

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/29/1995

Emphasis:

Case Closed: 10/24/1996


Related Activity
Type Activity Nr Safety Health
Accident 361117740
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,250 $0 $0 $0 $0 $1,250
Current Penalty $1,250 $0 $0 $0 $0 $1,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260416 A03 01/05/1996 01/10/1996 $1,250 $1,250 $0 01/16/1996 R - Review Commission  
2. 01001B Serious 19260651 B02 01/05/1996 01/10/1996 $0 $0 $0 01/16/1996 R - Review Commission  

Investigation Summary

Investigation Nr: 170670749
Event: 07/18/1995
ELECTRIC SHOCK - CONTACT WITH UNDERGROUND LINE THRU DIGGER

An employee was digging a ditch with a Ditchwitch. The ditch was for PVC electrical conduit for a lighting installation in a parking area at a new construction site. A 4000-volt underground power line that was encased in an existing 4-inch PVC conduit was buried in the general area where the employee was digging. Despite the presence of a junction box marked with a high-voltage warning, the employer had not requested the identification of the exact location of the underground line. Additionally, the employee was not wearing rubber insulating gloves. After the employee had been digging for about 3.7 meters, the Ditchwitch struck the power line, which was buried about 300 millimeters below the surface. The employee went over to see what had jammed the machine. The employee apparently placed his hand on the auger of the Ditchwitch and was electrocuted.

Keywords: ELECTRICAL, E C, UNDRGRD POWER LINE, DITCH, ELECTROCUTED, TRENCH DIGGER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 110089380 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.