Powered by GoogleTranslate

Inspection Detail

Inspection: 109470930 - Spartan Constructors, Inc

Inspection Information - Office: Atlanta West Area Office

 

Inspection Nr: 109470930
Report ID: 0418200
Date Opened: 02/04/1993

Site Address:
Spartan Constructors, Inc
238 Maysbridge Road
Rome, GA 30161

Mailing Address:
3412 Pierce Drive, Chamblee, GA 30341

Union Status: NonUnion

SIC:1541

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/30/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/24/1993


Related Activity
Type Activity Nr Safety Health
Accident 360825061
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 1 8
Current Violations 6 1 7
Initial Penalty $24,500 $0 $0 $900 $0 $25,400
Current Penalty $20,500 $0 $0 $900 $0 $21,400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 5A0001 07/28/1993 08/30/1993 $0 $4,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100119 H03 II 07/28/1993 08/23/1993 $2,250 $4,000 $0 I - Informal Settlement  
3. 01003 Serious 19100252 A02 II 07/28/1993 08/23/1993 $2,250 $2,250 $0 -  
4. 01004 Serious 19100252 A02 IIIA 07/28/1993 08/23/1993 $4,000 $2,250 $0 I - Informal Settlement  
5. 01005 Serious 19100252 A02 IV 07/28/1993 08/23/1993 $4,000 $4,000 $0 I - Informal Settlement  
6. 01006 Serious 19100252 A02 XIIIC 07/28/1993 08/23/1993 $4,000 $4,000 $0 I - Informal Settlement  
7. 01007 Serious 19100261 G22 07/28/1993 08/23/1993 $4,000 $4,000 $0 -  
8. 02001 Other 19040005 A 07/28/1993 08/23/1993 $900 $900 $0 -  

Investigation Summary

Investigation Nr: 922286
Event: 02/03/1993
Two employees killed, one injured by blowtank explosion

Employees #1, #2, and #3 were employed by a subcontractor hired to repair the vacuum breaker on a blowtank-accumulator. The peppermill personnel were responsible for completely purging the tank of all flammable and combustible vapors. The peppermill lab technician was assigned to take an atmospheric air sample of the tank--the normal procedure was to take an air sample only in the area where the work was to be done. After the air samples were taken, Employee #2 ignited an oxyacetylene torch. A small cut was made, followed by an explosion. Employee #1 was crushed to death by the falling steel stairway. Employee #2 was killed when he was blown over the side of the tank and fell 40 ft, landing on a piping system. Employee #3 was hospitalized for several days and released. The bottom portion of the accumulator tank was never tested for flammable vapors.

Keywords: FLAMMABLE VAPORS, WORK RULES, EXPLOSION, TANK, REPAIR, ACETYLENE TORCH, CONSTRUCTION, CRUSHED, FALL, FALLING OBJECT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109470930 Hospitalized injury Bruise/Contus/Abras Occupation not reported
2 109470930 Fatality Other Occupation not reported
3 109470930 Fatality Other Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close